Ammonia Detection
Sensitivity
25 to 800 PPM solid state sensor
25 to 500 PPM Electrochemical sensor
Ammonia Sensor
Metal oxide semiconductor
833 mW integral heater
Alumina ceramic base
100 mesh SUS 316 double gauge flame
arrestor or electrochemical sensor
Relays
Alarm, Pre-Alarm, and Auxiliary
(auxiliary relay operates at same time
as alarm relay)
Form C (SPDT), normally-open,
normally-closed, energized in
normally-open state.
Rated 5A, 115 VAC or 24 VDC
Outputs
Contacts for: alarm, pre-alarm, and
auxiliary relays, and external
temperature sensor
Operating Temperature
-50°F to 125°F Solid State Sensor
-10°F to 125°F Electrochemical Sensor
Operating Humidity
5% to 95% RH, non-condensing
Power Requirements
100 to 240VAC 60 Hz, 0.12 Amps max.
or 24 VDC, 0.58 Amps max.
or 16VAC, 0.65 Amps max.
Dimensions:
7-
1⁄2"H x 7
-
1⁄2"W x 4
-
1⁄2"D
Weight:
4 lbs.
Enclosure:
NEMA 4X rated, UL listed, CSA, IEC,
IP66