alarms. 
All  sensors  must  be  tested  after  installation  and 
periodically  thereafter.  Testing  methods  must  satisfy  the 
Authority  Having  Jurisdiction  (AHJ).  Sensors  offer 
maximum  performance  when  tested  and  maintained  in 
compliance with NFPA 72. 
The sensor can be tested in the following ways: 
A. Smoke Entry test: Aerosol Generator (Gemini 501) 
The  GEMINI  model  501  aerosol  generator  can  be  used 
for  smoke  entry  testing.  Set  the  generator  to  represent 
4%/ft  to  5%/ft  obscuration  as  described  in  the  GEMINI 
501  manual.  Using  the  bowl  shaped  applicator,  apply 
aerosol  until  the  panel  alarms.  Additionally,  canned 
aerosol  simulated  smoke  (canned  smoke  agent)  may  be 
used for smoke entry testing of the smoke detector. Tested 
and  approved  aerosol  smoke  products  are  the  Smoke 
Detector  Tester  model  25S  available  from  Home 
Safeguard  Industries  and  Chekkit  Smoke  Detector  Tester 
models  CHEK02  and  CHEK06  available  from  SDi.   
When  used  properly,  the  canned  smoke  agent  will  cause 
the  smoke  detector  to  go  into  alarm.  Refer  to  the 
manufacturer

s  published  instructions  for  proper  use  of 

the canned smoke agent. 
 
 
 
Canned  aerosol  simulated  smoke  (canned  smoke  agent) 
formulas will vary by manufacturer. Misuse or overuse of 
these products may have long term adverse effects on the 
smoke  detector.  Consult  the  canned  smoke  agent 
manufacturer

s  published  instructions  for  any  further 

warnings or caution statements. 
 
B.  Direct  Heat  Method  (Hair  Dryer  of  1000-1500  watts) 
YT202T only 
A hair dryer of 1000-1500 watts should be used to test the 
thermistors.  Direct  the  heat  toward  either  of  the  two 
thermistors,  holding  the  heat  source  approximately  12 
inches  from  the  detector  in  order  to  avoid  damaging  the 

plastic  housing.  The  detector  will  reset  only  after  it  has 
had  sufficient  time  to  cool.  Make  sure  both  thermistors 
are tested individually. 
A sensor that fails any of these tests should be cleaned as 
described  under  CLEANING,  and  retested.  If  the  sensor 
fails after cleaning, it must be replaced. 
When  testing  is  complete,  restore  the  system  to  normal 
operation and notify the proper authorities that the system 
is back in operation. 

CLEANING 

Before  removing  the  detector,  notify  the  proper 
authorities  that  the  smoke  detector  system  is  undergoing 
maintenance  and  will  be  temporarily  out  of  service. 
Disable  the  zone  or  system  undergoing  maintenance  to 
prevent unwanted alarms. 
1.

 

Remove the sensor to be cleaned from the system. 

2.

 

Remove the sensor cover by  pressing  firmly  on  each 
of the four removal tabs that hold the cover in place. 

3.

 

Vacuum  the  screen  carefully  without  removing  it.  If 
further  cleaning  is  required  continue  with  Step  4, 
otherwise skip to Step 7. 

4.

 

Remove  the  chamber  cover/screen  assembly  by 
pulling it straight out. 

5.

 

Use  a  vacuum  cleaner  or  compressed  air  to  remove 
dust and debris from the sensing chamber. 

6.

 

Reinstall  the  chamber  cover/screen  assembly  by 
sliding the edge over the sensing chamber. Turn until 
it is firmly in place. 

7.

 

Replace the  cover  using the LEDs to align  the  cover 
and  then  gently  pushing  it  until  it  locks  into  place. 
Make  sure  that  the  thermistors  do  not  become  bent 
under the cover on YT202T models. 

8.

 

Reinstall the detector. 

9.

 

Test the detector as described in TESTING. 

10.

 

Reconnect disabled circuits. 

11.

 

Notify  the  proper  authorities  that  the  system  is  back 
on line. 

 
 
 
 

THREE-YEAR LIMITED WARRANTY

 

Convoy  Security  warrants  its  enclosed  smoke  detector  to  be  free  from  defects  in  materials  and  workmanship  under  normal  use  and  service  for  a  period  of  three  years 
from date of manufacture. Convoy Security makes no other express warranty for this smoke detector. No agent, representative, dealer, or employee of the Company has 
the authority to increase or alter the obligations or limitations of this Warranty. The Company

s obligation of this Warranty shall be limited to the repair or replacement of 

any part of the smoke detector which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with 
the date of manufacture. After phoning Convoy Security

s technical support number for a Return Authorization number, send defective units postage prepaid to Convoy 

Security  local  representative  office.  Please  include  a  note  describing  the  malfunction  and  suspected  cause  of  failure. The  Company  shall  not  be  obligated  to  repair  or 
replace units which are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall 
the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage 
is caused by the Company

s negligence or fault. Some states do not allow the exclusion or limitation of incidental or consequential damages,  so the above limitation or 

exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state. 

 

FCC STATEMENT 

This device complies  with  part 15 of the FCC Rules. Operation is  subject to the following two conditions: (1) This device may not cause harmful interference, and (2) 
this device must accept any interference received, including interference that may cause undesired operation. 
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed 
to provide reasonable      protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, 
if not installed and used in accordance with the instructions,  may cause harmful interference to radio communications. However, there is no guarantee that interference 
will  not  occur  in  a  particular  installation.  If  this  equipment  does  cause  Harmful  interference  to  radio  or  television  reception,  which  can  be  determined  by  turning  the 
equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: 

  Reorient or relocate the receiving antenna. 

  Increase the separation between the equipment and receiver. 

 

Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. 

Please refer to insert for the Limitations of Fire Alarm Systems 