ALSPA PROFIBUS Field Bus Coupler
10. Diagnostics
(09/06)
Technical Manual
Page 10-3
10.3
MVS3007-4001 and MVS3007-4002 Fieldbus Coupler Indicator
LEDs
The MVS3007-4001 and MVS3007-4002 PROFIBUS Fieldbus Couplers
provide two LED indicators for diagnostic purposes. These are not
visible from the outside of the drive, but are visible on the edge of the
board when the Drive control door is open. They are viewed end-on as
shown in Figure 10-1) and have meanings as shown in Table 10-5.
On = Ready for operation
Slow flash = Watchdog acting
Off = Network found
Flickering = Baud rate seeking
Slow flash = Watchdog acting
On = Not yet configured
H3
H2
Figure 10-1 Diagnostic LEDs on the PROFIBUS board
Table 10-5 LED indication meaning
LED H2
LED H3 Description
On
On
Node address not yet configured
On Flickering
Searching for any network traffic.
On
Off
Network traffic found.
Pulsing Pulsing
Watchdog
time-out.
Depending on the setting of Switch S2 parameter P75.46 or
parameter P74.09 will display the state of the communications
without opening the drive to view the LEDs, see Section 7.4.10.
10.4
Spares and Re-order Information
The interface does not contain any user replaceable parts and must
be returned to the manufacturer for repair. Whole units should be
kept for spares.
Please contact customer support, or your local agent for details.
The MVS3007-4001 PROFIBUS board is no longer available.
The order number for the replacement PROFIBUS board is:
MVS3007-4002
Содержание ALSPA MV3000e
Страница 1: ...PROFIBUS Fieldbus Coupler MVS3007 ALSPA MV3000e Publication No T1694EN Rev 0004 06 06 ...
Страница 3: ...ALSPA PROFIBUS Field Bus Coupler 09 06 Technical Manual iii ...
Страница 73: ...ALSPA PROFIBUS Field Bus Coupler 8 Menu 75 Parameters 09 06 Technical Manual Page 8 13 ...
Страница 74: ......
Страница 106: ...Glossary ALSPA PROFIBUS Field Bus Coupler Glossary 2 Technical Manual 09 06 This page intentionally left blank ...
Страница 110: ...Block diagram ALSPA PROFIBUS Field Bus Coupler Page ii Technical Manual 06 06 09 06 This page intentionally left blank ...
Страница 112: ...Block diagram ALSPA PROFIBUS Field Bus Coupler Page iv Technical Manual 06 06 09 06 This page intentionally left blank ...