CONVECTAIR 8028-C09 Скачать руководство пользователя страница 20

 Page 20 

Indoor Unit 

Installation

Installation Instructions – Indoor unit 

PRIOR TO INSTALLATION

Before installing the indoor unit, refer to the 

label on the product box to make sure that the 

model number of the indoor unit matches the 

model number of the outdoor unit.

Step 1: Select installation location

Before installing the indoor unit, you must 

choose an appropriate location. The following 

are standards that will help you choose an 

appropriate location for the unit.

Proper installation locations meet the 

following standards:

 

Good air circulation

If no need the back holder to prop up
the unit:

Finishing the pipe and cable connections 
before mount the indoor unit on the wall.
If the instllation height is limited, 5cm from 
the ceiling is allowable, but this can lower
product performance. To ensure enough
space to install and remove the top air filter,
keep at least 10cm or more from the ceiling.

Need the back holder to prop up the unit:

If connecting pipe and cable with front panel
open, the minimum distance from ceiling is 
22cm or more, if connecting pipe and cable 
without front panel(remove it) , the minimum 
distance from ceiling is 11cm or more.

 

Convenient drainage
Noise from the unit will not disturb other 

people

 

Firm and solid—the location will not vibrate

 

Strong enough to support the weight of the 

unit

 

A location at least one meter from all other 

electrical devices (e.g., TV, radio, computer)

DO NOT

 install unit in the following 

locations:

 

Near any source of heat, steam, or 

combustible gas

 

Near flammable items such as curtains or 

clothing

 

Near any obstacle that might block air 

circulation

 

Near the doorway

 

In a location subject to direct sunlight

NOTE ABOUT WALL HOLE:

If there is no fixed refrigerant piping: 
While choosing a location, be aware that you 

should leave ample room for a wall hole (see 

Drill wall hole for connective piping 

step) 

for the signal cable and refrigerant piping 

that connect the indoor and outdoor units. 

The default position for all piping is the right 

side of the indoor unit (while facing the unit).
However, the unit can accommodate piping to 
both the left and right. 


 

Refer to the following diagram to ensure 

proper distance from walls and ceiling:

NOTE:

Step 2: Attach mounting plate to wall

The mounting plate is the device on which you 

will mount the indoor unit.

 

Remove the screw that attaches the mounting 

plate to the back of the indoor unit.

 

 

Secure the mounting plate to the wall with
the screws provided.  Make sure that mounting 
plate is flat against the wall. 

 

12cm (4.72in)

or more

2.3m (90.55in) or more

12cm (4.72in)

or more

Distance from ceiling is determinded 
by the installation method.

NOTE FOR CONCRETE OR BRICK WALLS:

If the wall is made of brick, concrete, or similar 

material, drill 5mm-diameter (0.2in-diameter) 

holes in the wall and insert the sleeve anchors 

provided. Then secure the mounting plate to 

the wall by tightening the screws directly into 

the clip anchors.

Screw

Indoor Unit Installation

Содержание 8028-C09

Страница 1: ...w air conditioning unit Make sure to save this manual for future reference Please check the applicable models technical data F GAS if any and manufacturer information from the Owner s Manual Product F...

Страница 2: ...Owner s Manual Table of Contents Safety Precautions 04 Care and Maintenance 12 Troubleshooting 14 1 Indoor unit display 08 2 Operating temperature 09 3 Other features 10 4 Setting angle of airflow 11...

Страница 3: ...t 27 Outdoor Unit Installation 27 1 Select installation location 27 2 Install drain joint 28 3 Anchor outdoor unit 28 4 Connect signal and power cables 30 Refrigerant Piping Connection 31 A Note on Pi...

Страница 4: ...s rods or other objects into the air inlet or outlet This may cause injury since the fan may be rotating at high speeds Do not use flammable sprays such as hair spray lacquer or paint near the unit Th...

Страница 5: ...exceeding 30mA and disconnection must be incorporated in the fixed wiring in accordance with the wiring rules For all electrical work follow all local and national wiring standards regulations and th...

Страница 6: ...o not install the unit within 1 meter 3 feet of any combustible materials Do not install the unit in a location that may be exposed to combustible gas leaks If combustible gas accumulates around the u...

Страница 7: ...ot be mixed with general household waste WARNING for Using R32 R290 Refrigerant 2 2 2 2 2 When flammable refrigerant are employed appliance shall be stored in a well ventilated area where the room siz...

Страница 8: ...ecifications and Features Indoor unit display Unit Specifications and Features for 3 seconds when TIMER OFF is set when defrosting for cooling heating units when Active Clean feature is turned on For...

Страница 9: ...C 30 C 32 F 86 F 10 C 32 C 50 F 90 F Outdoor Temperature 30 C 24 C 22 F 75 F 0 C 50 C 32 F 122 F 30 C 50 C 22 F 122 F To further optimize the performance of your unit do the following Keep doors and w...

Страница 10: ...the infrared remote is not included in this literature package Not all the functions are available for the air conditioner please check the indoor display and remote control of the unit you purchased...

Страница 11: ...ximum angle under heating capacity test CAUTION Do not put your fingers in or near the blower and suction side of the unit The high speed fan inside the unit may cause injury Fig A Fig B Fig C Setting...

Страница 12: ...low irregular and too much noisy so please clean the air filter as often as necessary Once the abnormal noise of air flow is heard please clean the air filter immediately 1 The air filter is on the to...

Страница 13: ...If you plan not to use your air conditioner for an extended period of time do the following Clean all filters Turn on FAN function until unit dries out completely Turn off the unit and disconnect the...

Страница 14: ...Troubleshooting The unit changes from COOL HEAT mode to FAN mode The indoor unit makes noises A rushing air sound may occur when the louver resets its position A squeaking sound may occur after runni...

Страница 15: ...customer service center Provide them with a detailed description of the unit malfunction as well as your model number Troubleshooting Troubleshooting When troubles occur please check the following po...

Страница 16: ...oor heating performance The outdoor temperature is extremely low Use auxiliary heating device Cold air is entering through doors and windows Make sure that all doors and windows are closed during use...

Страница 17: ...ized technician while installing the machine Mounting plate fixing screw Remote controller Fixing screw for remote controller holder optional Remote controller holder optional Drain joint for cooling...

Страница 18: ...oor Unit STEP 8 Wrap Piping and Cable not applicable for some locations in North America Connect Piping Prepare Drain Hose Connect Wiring not applicable for some locations in North America 4 5 6 7 8 9...

Страница 19: ...uirement of local and national standards The installation may be slightly different in different areas Wall Mounting Plate Power Cable Some Units Refrigerant Piping Signal Cable Remote Controller Drai...

Страница 20: ...cal devices e g TV radio computer DO NOT install unit in the following locations Near any source of heat steam or combustible gas Near flammable items such as curtains or clothing Near any obstacle th...

Страница 21: ...seal it when you finish the installation process CAUTION When drilling the wall hole make sure to avoid wires plumbing and other sensitive components NOTE When the gas side connective pipe is 16mm 5...

Страница 22: ...to the Refrigerant Piping Connection section of this manual for detailed instructions on pipe flaring and flare torque requirements technique etc NOTE ON PIPING ANGLE Refrigerant piping can exit the...

Страница 23: ...he unit See figure below This will create a slot through which your piping can exit the unit Use needle nose pliers if the plastic panel is too difficult to remove by hand 3 Use scissors to cut down t...

Страница 24: ...nst refrigerant tubing the compressor or any moving parts within the unit If the unit has an auxiliary electric heater it must be installed at least 1 meter 40in away from any combustible materials To...

Страница 25: ...e unit remove the plastic panel on the bottom left hand side ALL WIRING MUST BE PERFORMED STRICTLY IN ACCORDANCE WITH THE WIRING DIAGRAM LOCATED ON THE BACK OF THE INDOOR UNIT S FRONT PANEL 5 Feed the...

Страница 26: ...G THE WIRING CONNECTION PROCESS MAY DIFFER SLIGHTLY BETWEEN UNITS AND REGIONS Before passing the piping drain hose and the signal cable through the wall hole you must bundle them together to save spac...

Страница 27: ...ir outlet fan is at a 90 angle to the direction of the wind If needed build a barrier in front of the unit to protect it from extremely heavy winds See Figures below Strong wind Strong wind Strong win...

Страница 28: ...bber seal see Fig B do the following 1 Insert the drain joint into the hole in the base pan of the unit The drain joint will click in place 2 Connect a drain hose extension not included to the drain j...

Страница 29: ...Remove the nuts from expansion bolts and place outdoor unit on bolts 6 Put washer on each expansion bolt then replace the nuts 7 Using a wrench tighten each nut until snug WARNING WHEN DRILLING INTO C...

Страница 30: ...ock 5 Ground the unit in accordance with local codes 6 Be sure to size each wire allowing several inches longer than the required length for wiring 7 Use lock nuts to secure the conduit tubes BEFORE P...

Страница 31: ...et substances or gases other than the specified refrigerant enter the unit The presence of other gases or substances will lower the unit s capacity and can cause abnormally high pressure in the refrig...

Страница 32: ...downward angle to prevent burrs from falling into the pipe 2 Using a reamer or deburring tool remove all burrs from the cut section of the pipe Pipe Reamer Point down Step 3 Flare pipe ends Proper fl...

Страница 33: ...0 76 0 78 23 2 23 7 0 91 0 93 18 20 180 200kgf cm 32 39 320 390kgf cm 49 59 490 590kgf cm 57 71 570 710kgf cm 67 101 670 1010kgf cm 9 52 0 375 12 7 0 5 16 0 63 19 0 75 1 Unscrew the cover from the pa...

Страница 34: ...least 15 minutes or until the Compound Meter reads 76cmHG 10 Pa 2 3 4 5 5 6 Close the Low Pressure side of the manifold gauge and turn off the vacuum pump 7 Wait for 5 minutes then check that there ha...

Страница 35: ...0Btu h and 24000Btu h ADDITIONAL REFRIGERANT PER PIPE LENGTH Connective Pipe Length m Air Purging Method Additional Refrigerant Standard pipe length Vacuum Pump N A Standard pipe length Vacuum Pump Li...

Страница 36: ...Water Method Using a soft brush apply soapy water or liquid detergent to all pipe connection points on the indoor unit and outdoor unit The presence of bubbles indicates a leak Leak Detector Method If...

Страница 37: ...NECTIONS During operation the pressure of the refrigerant circuit will increase This may reveal leaks that were not present during your initial leak check Take time during the Test Run to double check...

Страница 38: ...ging bag Outdoor Unit 1 Cut the packing belt 2 Take the unit out of the carton 3 Remove the foam from the unit 4 Remove the packaging bag from the unit Packing Indoor unit 1 Put the indoor unit into t...

Страница 39: ......

Страница 40: ...cations are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details Any updates to the manual will be uploaded to the service website p...

Отзывы: