![Contronics HTR-10 Скачать руководство пользователя страница 5](http://html1.mh-extra.com/html/contronics/htr-10/htr-10_user-manual_2658972005.webp)
5
HTR-10
Change the configuration of the parameters:
Press and simultaneously for 3 seconds.
The screen will now flash.
Press or to change the setting.
Press and simultaneously for 3 seconds to confirm.
Press multiple times to return to the start screen.
Installation menu 1
Index
Setting
Minimum
Maximum
Factory setting
1
Humidity offset
-9 %
30 %
0 %
2
Temperature offset
-9 ºC
10 ºC
0 ºC
3
Minimum capacity
0 %
99 %
0 %
4
Maximum capacity
0 %
99 %
99 %
5
Bandwidth*
)
1 %
20 %
10 %
*) this setting cannot be read or changed in capacity mode.
Installation menu 2
Index
Setting
Minimum
Maximum
Factrory setting
11
Mode 0 = Capacity
0 %
99 %
99 %
11
Mode 1 = Humidity
(factory setting)
0 %
99 %
85 %
8. OPERATION
Configuring the humidity (in hygrostat mode) or capacity (in capacity mode):
Press for 3 seconds.
The upper screen shows the setting.
Press and simultaneously for 3 seconds.
The screen will now flash.
Change setting using or .
Press and simultaneously for 3 seconds to confirm.
Press return to the start screen.