Controls MVP-G342 Скачать руководство пользователя страница 12

 

11 

 

(7) 

Engine Safety Configuration 

Sender Check By-Pass (Default = 0:10) 

 

 

Oil Pressure Check (Default = Run) 

 

 

Oil Pressure Alarm Action (Default = Shutdown) 

 

 

Oil Pressure Alarm Delay (Default = 0:05) 

 

 

Temperature Check (Default = Run) 

 

 

Low Temperature Pre-Alarm (Default = 0 Deg.) 

 

 

Low Temperature Alarm (Default = 0 Deg.) 

 

 

High Temperature Pre-Alarm (Default = 240 Deg.) 

 

 

High Temperature Alarm (Default = 240 Deg.) 

 

 

Coolant Temperature Action (Default = Shutdown) 

 

 

Temperature Alarm Delay (Default = 0:05) 

 

 

Speed Limit (Default = 1600 rpm) 

 

 

Torque Derate Limit (Default = 50%) 

 

 

Low Oil Pressure Pre-Alarm (Default = 0 PSI) 

 

 

Low Oil Pressure Alarm (Default = 1 PSI) 

 

 

 

(8) 

Generator Safety Configuration 

Genset Rating (Default = 1 KW) 

 

 

Genset Derate (Default = 0%) 

 

 

AC Check Bypass (Default = 0:05) 

 

 

High Frequency Check (Default = Off) 

 

 

High Frequency Pre-alarm Setting (Default = 65.0 Hz) 

 

 

High Frequency Alarm Setting (Default = 67.0 Hz) 

 

 

High Frequency Alarm Delay (Default = 0:01) 

 

 

Low Frequency Check (Default = Run) 

 

 

Low Frequency Pre-alarm (Default = 55.0 Hz) 

 

 

Low Frequency Alarm (Default = 53.0 Hz) 

 

 

Low Frequency Alarm Delay (Default = 0:05) 

 

 

Overcurrent Check (Default = Run) 

 

 

Current Alarm Delay (Default = 0:05) 

 

 

Current Tolerance (Default = 10%) 

 

 

Voltage Check (Default = Run) 

 

 

 

(9) 

Module Configuration 

Low Power Mode 

 

 

Power Save Delay 

 

 

Pre-Alarms Displayed (Default = 4) 

 

 

Primary Run Source 

 

 

Secondary Run Source 

 

 

Check Run Criteria 

 

 

Clear Operation Log (Default = No) 

 

 

Clear Alarm Log (Default = No) 

 

 

Clear # of Starts 

 

 

Engine Run Criteria 

 

 

 

Содержание MVP-G342

Страница 1: ...______________________________________________________________________________________________________________________________________ Copyright Controls Inc P O Box 368 Sharon Center OH 44274 Phone 3...

Страница 2: ...CONNECTOR INFORMATION 5 ENGINE ALARMS CODES AND MESSAGES 7 ENGINE ECU ALARMS DE RATE SHUT DOWNS ALARM ANNUNCIATION AND CODE READER PANEL INDICATION LAMPS ACTIVE AND STORED ENGINE ECU CODES CONTROL PA...

Страница 3: ...gine make and model These settings are available in the CAN CONFIGURATION MENU Generator Safety Configuration Genset Rating Default 1 KW Genset Derate Default 0 AC Check Bypass Default 0 05 High Frequ...

Страница 4: ...3 INSTALLATION INFORMATION CONNECTOR INFORMATION...

Страница 5: ...4 BATTERY CAN HIGH CAN LOW N A FUEL LEVEL BATTERY 1 2 3 4 5 6 N A FUEL RUN N A N A OUTPUT 2 OUTPUT 3 1 2 3 4 5 6...

Страница 6: ...huts down the engine when it is not operating within normal parameters This includes more common shut downs like high engine temperature and low oil pressure but can encompass a large range of paramet...

Страница 7: ...anel also provides the ability to check the engine ECU for all ACTIVE and STORED engine ECU codes These codes can be viewed via the Active Codes and Stored Codes menus Engine Fault Lamp Engine Alarm L...

Страница 8: ...bles the alarm conditions Always enables the alarm constantly regardless of engine state 2 Alarm Delay The time period after Sender Check Bypass that the parameter must be on the alarm condition befor...

Страница 9: ...button to enter menu Press DOWN arrow button to reverse Exit Menu System Hold MENU button and press ENTER button To Change a Setting Press ENTER button to bring up brackets Press UP arrow button and D...

Страница 10: ...ressure View Engine Identification Engine Model View Engine Serial View Module Information Control Unit Part View Control Unit Software Version View Controller Setup Quick Setup 1 PASSWORD PROTECTED E...

Страница 11: ...guration Phase Type Voltage Type Generator Pole Pairs Generator Run Detect Activation Frequency Activation Delay Deactivation Frequency KWH Reset 4 Input Configuration Configure Selection Channels Mes...

Страница 12: ...8 Generator Safety Configuration Genset Rating Default 1 KW Genset Derate Default 0 AC Check Bypass Default 0 05 High Frequency Check Default Off High Frequency Pre alarm Setting Default 65 0 Hz High...

Страница 13: ...Transmit On Off Fuel Level Transmit On Off Voltage Transmit On Off Hours Transmit On Off Engine Status Transmit On Off Panel Status Transmit On Off Panel Information Transmit On Off Faults Transmit E...

Страница 14: ...15 Clutch Configuration Clutch 1 Engage Trip Default None Clutch 1 Engage Speed Default 800 rpm Clutch 1 Engage Load Default 0 Clutch 1 Engage Coolant Temperature Default 150 F Clutch 1 Engage Delay...

Отзывы: