MODULE CONFIGURATION
The Module Configuration menu is available to change the behavior of the control and clear several
of the log files.
Heading
Default
Range
Low Power Mode
Off
Off/On
Power Save Delay
2:00
2:00-5:00
Pre Alarms Displayed
3
0-3
Clear Operation Log
No
Yes/No
Clear Alarm Log
No
Yes/No
Clear Number of Starts
No
Yes/No
Engine Stopped <
50 RPM
1-400 RPM
Engine Running >
400 RPM
50-10000+ RPM
Factory Reset
No
Yes/No
DISPLAY CONFIGURATION
The Display Configuration menu is available to change the display characteristics of the module
Heading
Default
Range
Pressure & Temp Units
English
English/Metric
Performance Display
Off
On/Off
MAINTENANCE CONFIGURATION
The Maintenance Configuration menu is used to set up to four service intervals. The schedules can
be reset once the service is complete. If any schedule is not desired to be used, simply set the hours
to zero.
Heading
Default
Range
Maintenance Messages
No
Yes/No
Reset Interval A
No
Yes/No
Reset Interval B
No
Yes/No
Reset Interval C
No
Yes/No
Clear Break In Service
No
Yes/No
Schedule A
200 Hours
0-1000 Hours
Schedule B
500 Hours
0-1000 Hours
Schedule C
1000 Hours
0-1000 Hours
Break In Schedule
50 Hours
0-1000 Hours