                                                                                                                  - 12 - 

 

SERVICE/MAINTENANCE MESSAGES 

Maintenance intervals and messages can be enabled.   

 

  

 

 

 

 

 

 

Maintenance Intervals can be turned on allowing predetermined time intervals to be monitored for 
approaching and past service conditions.

  

Because new engines typically require a shorter interval to 

the first required service, the controller has two sets of programmable intervals.  The first service 
warning is set for 75 hours and the first service required alarm is set for 100 hours.  

 

 
Once the initial service time has been reset using the control panel maintenance menu, the service 
intervals will automatically be incremented to the Next Service Warning Interval and the Next Service 
Required Interval as programmed into the controller.

 

 

After resetting the interval, the controller will automatically add the engine hours and the interval time 
to show the operator exactly when service will be required next.

 

The control panel will display a yellow 

LED lamp and a message as the service intervals expire and maintenance is required.  

Expired service 

intervals 

will not stop

 the engine from running.

 

 

 

 

 

 

 

 

Maintenance Configuration Menu 

Service Interval Message On/Off 

 

Reset Interval Yes/No 

 

Service Warning Hour Selection 

 

Service Required Message Hour Selection 

 

Next Service Warning Interval Selection 

 

Next Required Message Hour Interval Selection 

 

1st Warning Service Hour Selection 

 

1st Service Required Message Hour Selection 

Содержание C3M-G7230-AS

Страница 1: ...C3M G7230 AS Revision 1 1 ______________________________________________________________________________________________________________________________________ Copyright Controls Inc P O Box 368 Shar...

Страница 2: ...PIN CONNECTOR PANEL CONNECTOR 5 16 PIN ENGINE HARNESS CONNECTOR FLOAT CONNECTOR 6 ENGINE ALARMS CODES AND MESSAGES 7 WARNINGS ALARMS ALARM EVENT LOG INDICATION LAMPS CONTROL PANEL SPECIFIC ALARMS AND...

Страница 3: ...e start wire is not grounded SLEEP MODE To minimize current draw the panel goes into a sleep mode two minutes after being set in auto mode In sleep mode the display goes blank and the red lamp blinks...

Страница 4: ...CONTROLS INCORPORATED C O N T R O L S Y S T E M S S O L U T I O N S 3 MODULE CONNECTORS Primary Connector 14 Pin Secondary Connector 23 Pin...

Страница 5: ...d Power to C3M 5 Preheat Signal 12 Battery Negative 6 Battery Positive 13 Fuel Level Sender Input 7 N A 14 Remote Start Input SECONDARY CONNECTOR 23 Pin Pin Function Pin Function Pin Function 1 9 16 2...

Страница 6: ...PE 16 Pin Engine Harness Connector Pin Function S Battery Positive F Battery Negative R Key On Power Fuel Run Signal J Preheat Signal D Crank Signal C Oil Pressure Sender Input H Engine Temperature Se...

Страница 7: ...rol panel Note Must use normally open contacts of the floats Controller will start engine when floats are closed Engine will stop upon float circuit opening SINGLE FLOAT Pin Function 1 Float Common 2...

Страница 8: ...ssage appears on the display identifying the cause ALARM EVENT LOG The Alarm Log creates an entry allowing the service and or operator to view the last 32 events An event is considered either a warnin...

Страница 9: ...CONTROLS INCORPORATED C O N T R O L S Y S T E M S S O L U T I O N S 8 INDICATION LAMPS The panel has two lamp indicators Engine Fault Shutdown Lamp Engine Warning Lamp...

Страница 10: ...ss Pre Alarm 15 0 100 PSI Low Oil Press Alarm 10 0 100 PSI Oil Press Alarm Delay 5 0 01 1 40 Sec Temperature Check Run Off Always Run Low Temp Pre Alarm 0 0 300 Deg F Low Temp Alarm 0 0 300 Deg F High...

Страница 11: ...f Relay 4 Function Crank 16 Pin Connector D Polarity Positive Initial State Off RELAY FUNCTIONS Available relays can be assigned for different uses a None Assign to none when not used b Pre Alarm Rela...

Страница 12: ...and while the engine is running Used to drive the engine s ECU circuit Also active when requesting active and stored J1939 codes m Custom 1 Reserved for OEM applications n Preheat Relay will be activ...

Страница 13: ...ntervals will automatically be incremented to the Next Service Warning Interval and the Next Service Required Interval as programmed into the controller After resetting the interval the controller wil...

Страница 14: ...nu Auto Start Delay Default 10 seconds Pre Heat Time Default 0 seconds Crank Time Default 10 seconds Crank Rest Time Default 10 seconds Warm Up Speed Default 800 rpm Warm Up Time Default 10 seconds Pr...

Страница 15: ...croll menu options Press UP arrow button to enter menu Press DOWN arrow button to reverse Exit Menu System Hold MENU button and press ENTER button To Change a Setting Press ENTER button to bring up br...

Страница 16: ...e Version View Controller Setup Menus Input Configuration 1 PASSWORD PROTECTED Output Configuration 2 Throttle Configuration 3 Engine Safety Configuration 4 Module Configuration 5 CAN Configuration 6...

Страница 17: ...Action Message When Active Delay Digital Input 8 Setup NO NC Action Message When Active Delay Digital Input 9 Setup NO NC Action Message When Active Delay 2 Output Configuration Relay Output 1 Setup F...

Страница 18: ...Engine Temperature Alarm Time Delay Selection Battery Volt Check On Off Low Battery Volt Pre Alarm Selection High Battery Volt Pre Alarm Selection Battery Volt Trim Setting Over Speed Alarm On Off Ove...

Страница 19: ...ge Delay Selection Recharge Run Time Selection Next Recharge Time Interval Selection 8 Auto Operation Settings Start Stop Input Floats Transducer Menu options changed based on start stop input selecte...

Страница 20: ...tch Configuration 1 Engage Trip 1 Engage Speed 1 Engage Load 1 Engage Delay 1 Engage Interval 1 Release Trip 1 Release Speed 1 Release Load 1 Release Delay 1 Release Interval 2 Engage Trip 2 Engage Sp...

Отзывы: