ASSEMBLING
The actuator can be mounted in the positions shown picture below:
It is advisable to use the motorized valve with MVHT spacer, in order
to reduce the actuator working temperature in case of fluids at high
temperatures (approximately > 120° C) in the valve body. For fluids
over 160 °C avoid mounting the actuator in vertical position on the
valve so as to avoid the direct exposure to heat sources.
For further information look at mounting instructions (MVH56Ex_
DIM262).
MAINTENANCE
The actuator is maintenance-free.
ACCESSORIES
DMVE
Endpoint Auxiliary Switches
248
Yoke Heater (Suggested when the fluid temperature is
below 0°C)
GMVHAC Insulation shell for MVH.A/C actuators
ELECTRIC CONNECTIONS
Carry out the electrical connections by removing the cover, in com-
pliance with the rules in force.
The actuator is equipped with a 8 poles removable terminal block;
the each pole of the plug is clearly marked and the same label are
reported on the electric board. Before powering up the actuator
make sure the plug is properly connected to the board and the label
on the plugs and on the board match.
Label
Description Function Cable type Max wire
Length
L1
24Vac/dc
Power
Supply
AWG 16 ( min
1mm
2
- max
1.5mm
2)
75m
Ln
0V
Y
0-10Vdc
Modulating
Control
Input
AWG 20 ( min
0,5mm
2
- max
1.5mm
2)
200m
M
0V (Common)
Y1
Open
Floating
Control
Input
AWG 20 ( min
0,5mm
2
- max
1.5mm
2)
200m
Y2
Close
V+
16 Vdc
Voltage
Output max
25mA
AWG 20 ( min
0,5mm
2
- max
1.5mm
2)
200m
M
0V (Common)
U
2-10Vdc
Feedback
Output
Signal
AWG 20 ( min
0,5mm
2
- max
1.5mm
2)
200m
M
0V (Common)
Controller(*)
3-point floating control
(sink connection)
0V
Y2
Ln
MVE
Y1
OPEN
24Vac/24Vdc
L1
CLOSE
3-point floating control
(source connection)
24Vac
0V
Controller(*)
OPEN
CLOSE
MVE
L1
Ln
Y1
Y2