ELECTRIC CONNECTIONS

Remove the cover screw with a screwdriver and then remove the 

cover as shown in the picture beside.

The actuator is equipped with a 8 poles removable terminal block; 

the each pole of the plug is clearly marked and the same label are 

reported on the electronic board. Before powering up the actuator 

make sure the plug is properly connected to the board and the label 

on the plugs and on the board match.

 

Use PG13,5 cable gland (not supplied).

Linkage

MVE

MVES

Current Controlli valves 

 

(except for 2TGB.F/3TGB.F PN16)

(not required)

/

2TGB.F/3TGB.F PN16

/

(not required)

Controlli valves with threaded M40 

connections

 

(except for VSB/VMB/VSBF/VMBF 

PN16)

AG51

/

VSB/VMB/ VSBF/VMBF PN16

AG52

AG63

Other manufacturers

Landis *

AG70-10 

 

AG70-14

/

Danfoss (VR/VF (S) models)

AG60-07

/

TAC DN15-V298

AG 60-08

/

TAC DN15-V2XX/V3XX

AG 60-09

/

Honeywell**

AG 60-10

/

Airtek

AG 60-11/

AG60-12

/

Johnson Controls code VB7816-

2111

AG 66

/

Johnson Controls code BM-3018-

3300

AG 67

/

Tac Venta

(not required)

/

(/) this model can not be assembled

(*)  AG70-10 for valves having stem Ø 10mm

 

AG70-14 for valves having stem Ø 14mm

(**) valid for the following models: M6: V176A. B, V538C                                               

1/4”: V5011A

 

ASSEMBLING

The actuator can be mounted with any orientation but never up-side 

down.  When the fluid temperature exceed 120°C the actuator shall 

be mounted leaning 45°.

N4170-17

T fluid ≥ 120°C

T fluid MAX 120°C

T fluid ≥ 120°C

To mount the actuator on to a valve, position the valve stem to the 

bottom of its travel,  slide the actuator onto the valve neck, adjusting 

with the manual override the screw jack position so the square nut 

on the valve spindle fits into the groove on the cross bar. Then slide 

the brace into the groove on the valve neck and secure the nuts.

See mounting instructions for full details (MVE_DIM223).

MAINTENANCE

The actuator is free of maintenance.

ACCESSORIES

DMVE

  

End point auxiliary switches (electrical rate 24V AC/DC, 

4A max)

248

 

Yoke heater (suggested when the fluid temperature is be-

low 0°C)

GMVE

 

Thermal insulation for MVE actuators

GMVE.S

  Thermal insulation for MVE.S actuators

1

st

 Issue rev. a

04/2016

DBL483e

Page 3

Содержание MVE522

Страница 1: ...anism convert the motor revolutions into accurate and repeatable linear movements Control Signal MVE can be controlled by one of 2 main control types 3 point floating Modulating or proportional signal...

Страница 2: ...pply voltage L1 Ln AC 24Vac 20 50 60Hz DC 22 30Vdc Reference Ln Power consumption running 25VA 10W Power consumption holding 10VA 4W Running time Modulating 5 15mm 60s Modulating 15 25mm Modulating 25...

Страница 3: ...3300 AG 67 Tac Venta not required this model can not be assembled AG70 10 for valves having stem 10mm AG70 14 for valves having stem 14mm valid for the following models M6 V176A B V538C 1 4 V5011A AS...

Страница 4: ...ing control sink connection 0V Y2 Ln MVE Y1 OPEN 24Vac 24Vdc L1 CLOSE 3 point floating control source connection 24Vac 0V Controller OPEN CLOSE MVE L1 Ln Y1 Y2 COMMAND COMMAND Controller MVE 24Vac 24V...

Страница 5: ...rol 0 5Vdc with DIP n 4 OFF only Sequence Control 2 6Vdc with DIP n 4 ON only DIP n 3 ON only Sequence Control 5 10Vdc with DIP n 4 OFF only Sequence Control 6 10Vdc with DIP n 4 ON only DIP n 3 ON on...

Страница 6: ...tial position still signalling the anomaly until it is not within 60mm The actuator does not calibrate the stroke after 10s wrong range Valve with a stroke length longer than 60mm Remove power and pow...

Страница 7: ...tor arrived at the extreme point of the stroke read 2 GREEN BLINKING The actuator arrived at the intermediate point of the stroke read 3 RED GREEN BLINKING The actuator is reading the stroke or it is...