End Point Auxiliary Switches (with accessory DMVE)

End  point  switches  change  over  when  the  valve  is  fully  open  or 

closed. They are free contacts with 24V AC/DC, 4A max voltage on 

terminals. End point switches can be utilized to indicate valve stroke 

end  positions  and  for  relay  control  of  additional  plant  equipment. 

When the actuators are controlled individually or in sequence, it is 

possible  to  use  the  end  switches  to  toggle  when  the  valve  is  fully 

open or fully closed. The auxiliary switch position according to con

-

trol signal (Y) is shown in the picture below.

Control signal (Y)

Relay 

KC1

Relay 

KC2

0-0,5Vdc

KC1 to K2

KC2 to K3

0,5-9,5Vdc

KC1 to K1

KC2 to K3

9,5-10Vdc

KC1 to K1

KC2 to K4

K1    K2  KC1

K1    K2  KC1

End point position

End point position

DMVE

RELE' DI CHIUSURA

RELE' DI APERTURA

K3    K4  KC2

Posizione di fine corsa

Posizione di fine corsa

K3    K4  KC2

OPENING RELAY

CLOSING RELAY

DMVE

Diagnostic

The actuator is provided with a self diagnostic algorithm able to de

-

tect faulty conditions:

• 

stroke calibration out of range 5-60mm;

• 

unexpected stall condition (e.g. valve stuck or extra stroke due 

to actuator link loose);

• 

voltage supply out of range. 

These faulty conditions are signalled through the GREEN and RED LED 

on the electronic board blinking accordingly (see Diagnostic – Alarm 

Function Table).

IP65

Protection against water and solid object IP65 is guaranteed by in

-

ternal seals, IP65 cable gland and the proper engineering of the en

-

closure.

One IP65 PG13,5 cable gland and one IP65 PG13,5 plug are supplied 

with the actuator.

TECHNICAL FEATURES

DESCRIPTION

MVE522-65 

MVE522S-65

Supply voltage L1 Ln

AC: 24Vac ±20% 50-60Hz

 

DC: 22-30Vdc (Reference Ln)

Power consumption 

(running)

25VA / 10W

Power consumption 

(holding)

10VA / 4W

Running 

time

Modulating

60 s

Floating

Transformer Size [VA]

50

Stroke

5-60 mm (limited to 30 mm for MVE522S-65)

Force

2200 N

Duty cycle

max 50%/60 minutes

Analogue input Y M

voltage 0-10Vdc - impedance > 100kΩ 

(range: 0-10Vdc, 2-10Vdc, 0-5/2-6Vdc, 

5-10/6-10Vdc)

 

500Ω (range 4-20mA)

Digital inputs Y1 Y2

connection to L1 or Ln when powered in AC 

 

connection to Ln only when powered in DC

Output V+

voltage 16Vdc ± 0,5Vdc 

max load 25mA, 

Output U

voltage 2-10Vdc (0-100%) 

max load 2mA

Number of cycles of 

manual action

6.000

Number of cycles of 

automatic action

100.000

Type of action

type 1

Type of movement

linear

Room temperature

operation -10T55°C; storage -20T55°C

Room Humidity

max 90% R.H.

Protection degree

Nema 2 (*) / IP65

Insulation class

Printed Circuit Board

FR4 (material)

 

PLC (Performance Level Categories) = 3

 

PTI (Proof Tracking Index) = 175 - 249V

 

CTI (Comparative Tracking Index) = PTI

 

Pollution Degree = 2

Standard

Emission/Immunity EMC 2014/30/UE 

according to EN 61326-1:2013 standard

Material

housing: aluminium - cover: ABS plastic

Colour

aluminium / white

Weight [kg]

1,7 (MVE522-65); 1,6 (MVE522S-65)

Date code

yy/ww

*To guarantee “Nema Type 2” protection:

• 

use flexible metal conduit (not supplied);

• 

Push the listed conduit fitting device over the actuator’s cable 

to butt against the enclosure. Screw in conduit connector. Jack

-

et the actuators input wiring with listed flexible conduit. Properly 

terminate the conduit in a suitable junction box.

1

st

 Issue rev. c

06/2020

DBL567e

Page 2

Содержание MVE522-65

Страница 1: ...ignal MVE522 65 can be controlled by one of 2 main control types 3 point floating Modulating or proportional signal with filed selectable range e g 0 10Vdc 2 10Vdc 0 5 2 6Vdc 5 10 6 10Vdc and 4 20mA M...

Страница 2: ...CHNICAL FEATURES DESCRIPTION MVE522 65 MVE522S 65 Supply voltage L1 Ln AC 24Vac 20 50 60Hz DC 22 30Vdc Reference Ln Power consumption running 25VA 10W Power consumption holding 10VA 4W Running time Mo...

Страница 3: ...powering up the actuator make sure the plug is properly connected to the board and the label on the plugs and on the board match Use cable gland IP65 PG13 5 model ASSEMBLING The actuator can be mounte...

Страница 4: ...hile fixing the terminal block Matching between MVE terminal block and others Controlli actuators WIRING DIAGRAMS 3 point floating control sink connection Controller 3 point floating control sink conn...

Страница 5: ...FF only Modulating Control 2 10Vdc DIP n 2 OFF only 5 Sequence Control 0 5Vdc with DIP n 4 OFF only Sequence Control 2 6Vdc with DIP n 4 ON only DIP n 3 ON only Sequence Control 5 10Vdc with DIP n 4 O...

Страница 6: ...tial position still signalling the anomaly until it is not within 60mm The actuator does not calibrate the stroke after 10s wrong range Valve with a stroke length longer than 60mm Remove power and pow...

Страница 7: ...troke read 2 GREEN BLINKING The actuator arrived at the intermediate point of the stroke read 3 RED GREEN BLINKING The actuator is reading the stroke or it is going to initial position 4 RED GREEN ON...

Отзывы: