APPLICATION AND USE

MVE522-65 is a flexible electro mechanical actuator for the control 

of two and three-way globe valves in:

• 

heating and cooling systems;

• 

Air Handling Units;

• 

district heating plants;

• 

industrial temperature control systems.

The actuator can be controlled either by a proportional (modulat

-

ing) signal or by an increase/decrease (Floating) signal.

It is easy to mount and connect the actuator. Direct mounting is pos

-

sible to any CONTROLLI flanged valve. Linkage kits are available for 

CONTROLLI threaded valves as well as for valves of other manufac

-

turers (table p. 3). The actuator has a fine resolution (500 steps on the 

full stroke range) for exacting fluid control and it is able to self-cali

-

brate on a different stroke without the need of any user action (this 

function is DIP switch selectable on the field). 

MVE522-65 has intelligent behaviour and alarm functionality in case 

of unexpected operation, feedback of alarms to the user is provided 

by LEDs (GREEN and RED) on the control board.

N.B.: Do not use the actuator if not coupled with its relating valve.

MVE522-65 is suitable for harsh environment requiring IP65 protection 

degree.

OPERATION

The  actuator  translates  the  control  signal  (modulating  or  3  point 

floating) from the controller into a valve position. A modern brushless 

DC motor in the actuator drive a gear train and a worm gear – screw 

jack  mechanism  convert  the  motor  revolutions  into  accurate  and 

repeatable linear movements.

Control Signal

MVE522-65 can be controlled by one of 2 main control types:

• 

3 point floating ;

• 

Modulating (or proportional) signal with filed selectable 

range (e.g., 0-10Vdc, 2-10Vdc, 0-5/2-6Vdc, 5-10/6-10Vdc and 

4-20mA).

Manual Override

There is a manual operation handle on the actuator. When it is low

-

ered (manual override ON), the power supply to the motor power 

stage circuitry is cut and the motor stops. The actuator can be oper

-

ated manually and the valve positioned accordingly.

The manual override lever stays in position until it is raised again, then 

board and motor will be powered again. At the end of this operation 

the actuator moves to initial position (on the basis of DIP n. 1 setting) 

then  it  follows  the  control  signal.  When  the  manual  override  is  en

-

gaged the GREEN and the RED LED are ON.

Manual operation handle can also be used to modify any DIP switch 

setting or as re-set function after any alarm occurrence.

The actuator is supplied with the manual override lowered (ON). It 

is not necessary to remove power supply to modify DIP switches set

-

ting.

Position Feedback

The actuator utilizes a 2-10Vdc position feedback (look at DIP n. 1 

setting).

Calibration

The actuator has both auto and manual stroke calibration, DIP n. 7. 

In factory delivery the auto stroke calibration is enabled – manual 

calibration is not necessary unless maintenance is required on the 

valve or certain alarm functions are desired.

MODEL

FORCE 

[N]

POWER 

SUPPLY

DESCRIPTION

MVE522-65 

2200

24Vac/dc

long yoke, modulating/

floating control, IP65

MVE522S-65 

2200

24Vac/dc

short yoke, modulating/

floating control, IP65

1

st

 Issue rev. c

06/2020

DBL567e

Page 1

 The device contains electrical and electronic components and is not allowed to be disposed 

of as household refuse. All locally valid regulations and requirements must be observed.

Содержание MVE522-65

Страница 1: ...ignal MVE522 65 can be controlled by one of 2 main control types 3 point floating Modulating or proportional signal with filed selectable range e g 0 10Vdc 2 10Vdc 0 5 2 6Vdc 5 10 6 10Vdc and 4 20mA M...

Страница 2: ...CHNICAL FEATURES DESCRIPTION MVE522 65 MVE522S 65 Supply voltage L1 Ln AC 24Vac 20 50 60Hz DC 22 30Vdc Reference Ln Power consumption running 25VA 10W Power consumption holding 10VA 4W Running time Mo...

Страница 3: ...powering up the actuator make sure the plug is properly connected to the board and the label on the plugs and on the board match Use cable gland IP65 PG13 5 model ASSEMBLING The actuator can be mounte...

Страница 4: ...hile fixing the terminal block Matching between MVE terminal block and others Controlli actuators WIRING DIAGRAMS 3 point floating control sink connection Controller 3 point floating control sink conn...

Страница 5: ...FF only Modulating Control 2 10Vdc DIP n 2 OFF only 5 Sequence Control 0 5Vdc with DIP n 4 OFF only Sequence Control 2 6Vdc with DIP n 4 ON only DIP n 3 ON only Sequence Control 5 10Vdc with DIP n 4 O...

Страница 6: ...tial position still signalling the anomaly until it is not within 60mm The actuator does not calibrate the stroke after 10s wrong range Valve with a stroke length longer than 60mm Remove power and pow...

Страница 7: ...troke read 2 GREEN BLINKING The actuator arrived at the intermediate point of the stroke read 3 RED GREEN BLINKING The actuator is reading the stroke or it is going to initial position 4 RED GREEN ON...