Control Techniques DRIVE CENTRE 306C Скачать руководство пользователя страница 5

RS422/485 COMMS PORT

The 306 has one RS422/485 port. This port can be configured to act as either

RS422 or RS485.

5

DH485 COMMUNICATIONS

The 306’s RS422/485 COMMS port can also be used for Allen Bradley

DH485 communications.

WARNING

DO NOT

use a standard DH485 cable to connect this port to Allen

Bradley equipment. 

CTVue to AB SLC 500

24V

-

TxA

3, 8

COMM

-

TxB

4, 7

SHIELD

4

COMM

6

TxEN

5

TxEN

5

COMM

-

RxB

4, 7

24V

-

RxA

3, 8

B

2

TxA

2

A

1

TxB

1

Name

RJ45: A-B

Name

RJ45: CTVue

Connections

RS422/485 4-WIRE

CONNECTIONS

RS485 2-WIRE

CONNECTIONS

S

OFTWARE

/U

NIT

O

PERATION

CTVue CONFIGURATOR SOFTWARE

CTVue Configurator software is available as a free download from Control

Techniques’ website or it can be ordered on a CD, see “Ordering Information”
for part number. The latest version of the software is always available from the
website, and updating your copy is free.

DISPLAY

This operator interface uses a liquid crystal display (LCD) for displaying text

and graphics. The display utilizes a cold cathode fluorescent tube (CCFL) for
lighting the display. The CCFL tubes can be dimmed for low light conditions.

These CCFL tubes have a limited lifetime. Backlight lifetime is based upon

the amount of time the display is turned on at full intensity. Turning the
backlight off when the display is not in use can extend the lifetime of your
backlight. This can be accomplished through the CTVue Configurator software
when programming your unit.

KEYPAD

The 306 keypad consists of five keys that can be used for on-screen menus.

TOUCHSCREEN

This operator interface utilizes a resistive analog touchscreen for user input.

The unit will only produce an audible tone (beep) when a touch on an active
touchscreen cell is sensed. The touchscreen is fully functional as soon as the
operator interface is initialized, and can be operated with gloved hands.

FRONT PANEL LEDS

There are three front panel LEDs. Shown below is the default status of 

the LEDs.

1

The operator interface is shipped without a configuration. After
downloading a configuration, if the light remains in the flashing state
continuously, try cycling power. If the LED still continues to flash, try
downloading a configuration again.

2

Do not turn off power to the unit while this light is flickering. The unit

writes data in two minute intervals. Later Microsoft operating systems will
not lock the drive unless they need to write data; Windows 98 may lock the
drive any time it is mounted, thereby interfering with logging. Refer to
“Mounting the CompactFlash” in the CTVue Configurator User Manual.

TROUBLESHOOTING YOUR 306

If for any reason you have trouble operating, connecting, or simply have

questions concerning your new 306, contact Control Techniques’ technical
support. For contact information, refer to the front page of this bulletin for
phone and fax numbers.

EMAIL: [email protected]
Web Site: http://www.emersonct.com

Valid configuration is loaded and there are no alarms present.

STEADY

A tag is in an alarm state.

FLASHING

GREEN (BOTTOM)

Valid CompactFlash card present.

STEADY

YELLOW (MIDDLE)

Unit is powered and running an application.

Unit is in the boot loader, no valid configuration is loaded.

1

LED INDICATION

RED (TOP, LABELED “PWR”)

CompactFlash card being checked.

No CompactFlash card is present.

FLICKERING

FLASHING

RAPIDLY

OFF

STEADY

FLASHING

FLASHING

SLOWLY

Incorrectly formatted CompactFlash card present.

Unit is writing to the CompactFlash, either because it is storing
data, or because the PC connected via the USB port has
locked the drive.

2