background image

© 2000 CONTRIVE • B14

50.EN  

06

1

7

 

2

 

www.contrive.it 

 

 

 

 

 

 

[mm]

 

WIRING DIAGRAM

 

 

1

  PO

SITIVE TERMINAL

 

 

USUALLY CONNECTED TO

 

GROUND

 

2

 

NEGATIVE TERMINAL

 

 

USUALLY CONNECTED TO

 

AMPLIFIER INPUT

 

 

CONNECTION WITH 

REVERSED POLARITY DOES NOT DAMAGE 

THE DETECTOR BUT PRODUCES NO USEFUL FLAME SIGNAL

 

 
 

CLASS II DEVICE

 

CONNECTION TO PROTEC

TION GROUND IS NOT REQUIRED

 

 

TECHNICAL DATA

 

 

 

SPECTRAL RESPONSE

 

185 … 260 nm

 

 

OPERATING VOLTAGE

 

200 … 280 V

AC

 

 

DISCHARGE CURRENT

 

1 mA

 

 

PEAK DISCHARGE CURRENT

 

30 mA

 

 

RECOVERY TIME

 

2Oµs 

@ 10% DUTY CYCLE

 

 

OPERATING TEMPERATURE

 

-

20 … +

90°C 

 

UV TUBE TEMPERATURE

 

125°C 

MAX

 

 

PROTECTION CLASS

 

IP65 

 

OPERATING LIFE

 

1

 

> 10.000 hours 

@ 50°C / 1mA

 

 

VIBRATION

 

0,5 G 

MAX

 

 

RELATIVE HUMIDITY

 

NON CONDENSING

  

10 … 90% 

 

 MOUNTING POSITION

 2

 

ANY 

1

 

 WEIGHT 

150 g 

MAX

 

 

1

 

UP TO 100.000 hours @25°C

 

 

2

 

DO  NOT  INSTALL  ON  TOP  IN  VERTICAL  POSITION  WHEN 

COMBUSTION PRODUCTS CAN FILL THE VOLUME IN FRONT 

OF THE SENSOR

 

 

DIMENSIONS

 

THERMAL INSULATING CASE Ø

 35 x 

80

 mm 

 

1

 

DIN43650 

– 

ISO4400 CONNECTOR

 

 

2 POLES + EARTH 

– 

PG11

 

 

2

 

DIN43650 

– 

ISO4400 SOCKET

 

 

2 POLES + EARTH

 

3

 

OPTIONAL COOLING

 

 

CONNECTION ¼“

 

4

 

BURNER HEAD

 

 

CONNECTION ¾” 

 

FRONT SIDE OF THE SENSOR IS SEALED WITH EPOXY RESIN  

THERE IS NO NEED FOR

 

ADDITIONAL QUARTZ GLASS

 

 

NOTICE 

 

When Contrive products are combined with equipment manufactured by others and/or integrated into systems 

designed or manufactured by others, the Contrive warranty pertains only to Contrive products and not to any other 

equipment or to the combined system or its overall performance. Certification invalid or not applicable in such cases. 

 