EMM-R4h EMM-
μ
4h
instruction manual
IM441-U v0.7
pag. 11
t < delay
Digital
output
Threshold HI
delay
Hysteresis HI
Alarm
SET THE DELAY TO THE DIGITAL OUTPUT ACTIVATION
Now it’s possible to set the delay that will pass between the alarm condition set and the activation of digital output. On
E
display will appear
ALR DLY
and the value expressed in seconds (range 1÷900). The modification of the value is done
in the same way of the threshold set. With the confirmation (
A
key) the set is complete.
The programming will be referred to the digital output indicated on
E
display (
DO1
o
DO2
).
With only the HI threshold set, the alarm condition is activated when the parameter set in alarm exceed the threshold.
The digital output is enabled only if the alarm condition remain activated for all delay time set. From the activation of the
digital output, the restore is automatic when the parameter decreases below the hysteresis value.
With only the LO threshold set, the alarm condition is activated when the parameter set in alarm drop below the
threshold. The digital output is enabled only if the alarm condition remain activated for all delay time set. From the
activation of the digital output, the restore is automatic when the parameter grow above the hysteresis value.
With both LO and HI threshold set, the alarm condition is activated when the parameter set in alarm is outside from the
values band limited by LO and HI thresholds
.
The digital output is enabled only if the alarm condition remain activated for
all delay time set. From the activation of the digital output, the restore is automatic when the parameter return inside the
values band limited by LO and HI thresholds.
t < delay
Digital
output
Threshold LO
delay
Hysteresis LO
Threshold HI
Alarm
delay
Hysteresis HI
t < delay
Digital
output
Threshold LO
delay
Hysteresis LO
Alarm
Functioning for
exceeding the
maximum threshold
Functioning for
dropping above
minimum threshold
Functioning for
exceeding or dropping
by the band defined by
maximum and
minimum threshold