![Contrec 515 Скачать руководство пользователя страница 62](http://html.mh-extra.com/html/contrec/515/515_operation-manual_2658179062.webp)
Communications
54
515 HC04 - 8 June 2007
Figure 17 RS-232 Cable Connections to a Computer
Note:
The instrument requires a cable with straight-through connections.
Do not use a null modem cable for RS-232 connection to a computer.
RS-485 Port (Advanced Option only)
The RS-485 port enables communication with multiple devices. Each
device has a unique address so that the “master” device can communicate
with specific “slave” devices.
On RS-485 links, an external terminating resistor must be connected at the
furthest end of the cable. When multiple instruments are connected, they
should be “daisy chained” in a multidrop configuration as shown in Figure
18. Up to 32 units can be connected to the interface at a maximum distance
of 1200 metres.
Figure 18 RS-485 Connections
Instrument
2
3
5
7
8
TxD
RxD
GND
CTS
RTS
DB9
Computer/Printer
3
2
7
4
5
RxD
TxD
GND
RTS
CTS
DB25
2
3
5
7
8
DB9
Common
Optional
Optional
Twisted Pair
Load
120 ohms
Gnd
Gnd
Host
Computer
Comms
Gnd
+
-
+
-
+
-
Instrument
Instrument
19 20 21
19 20 21
Содержание 515
Страница 4: ...iv 515 HC04 8 June 2007 ...
Страница 8: ...viii 515 HC04 8 June 2007 ...
Страница 16: ...Introduction 8 515 HC04 8 June 2007 ...
Страница 60: ...Instrument Calibration 52 515 HC04 8 June 2007 ...
Страница 80: ...Communications 72 515 HC04 8 June 2007 ...
Страница 82: ...74 515 HC04 8 June 2007 ...
Страница 88: ...80 515 HC04 8 June 2007 ...