6.0 ADJUSTMENTS

6.1  PILOT BURNER ADJUSTMENT

Remove the pilot screw cap.  Adjust the pilot screw to provide properly 
sized fl ame. Turn in a clockwise direction to reduce the gas fl ow.
Re-install the pilot screw cap.

Inlet pressure can be checked by turning screw (A) 
counter-clockwise until loosened and then placing pressure 
gauge tubing over the test point. Gauge should read 7” 
(minimum 4.5”) water column for natural gas or 13” (11” minimum) 
water column for propane. Check that main burner is operating on “HI”.

Outlet pressure can be checked the same as above using screw (B). 
Gauge should read 3.5” water column for natural gas or 10” water 
column for propane. Check that main burner is operating on “HI”.

AFTER TAKING PRESSURE READINGS, TIGHTEN 
SCREWS FIRMLY TO SEAL. DO NOT OVER 
TORQUE. LEAK TEST.

39.6

PILOT 

BURNER

THERMOCOUPLE

THERMOPILE

  

PI

L

O

T

PILOT SCREW

A

B

6.2 VENTURI 

ADJUSTMENT

This appliance has an air shutter that has been factory set open according 
to the chart below:

Regardless of venturi orientation, closing the air shutter will cause a more 
yellow flame, but can lead to carboning. Opening the air shutter will cause a 
more blue flame, but can cause flame lifting from the burner ports. The 
flame may not appear yellow immediately; allow 15 to 30 minutes for the 
final flame colour to be established. 

AIR SHUTTER ADJUSTMENT MUST ONLY BE DONE BY A QUALIFIED 
INSTALLER!

AIR 
SHUTTER 
OPENING

VENTURI
BURNER

ORIFICE

49.1

AIR SHUTTER SETTING

3" / 3" Liner System

2" / 3" Liner System

NG

1/16”

1/8"

LP

3/16”

5/16"

This appliance is approved for use with a 2" liner for air intake and a 3" liner for exhaust. For best performance, however, 
it is recommended to use two 3" liners.

Содержание CDIZC - N

Страница 1: ...r gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the supplier This appliance may be installed as an OEM installation in man...

Страница 2: ...REMOVAL AND INSTALLATION 13 4 3 LOG PLACEMENT 14 4 4 GLOWING EMBERS 14 4 5 LOGO PLACEMENT 15 4 6 ALUMINUM EXTRUSION TRIM KIT INSTALLATION 15 5 0 OPERATION 16 6 0 ADJUSTMENTS 17 6 1 PILOT BURNER ADJUST...

Страница 3: ...IMNEY CONNECTION section Trim see ALUMINUM EXTRUSION TRIM KIT INSTALLATION section Door see DOOR REMOVAL AND INSTALLATION section Rating Plate see RATING PLATE INFORMATION section Logs see LOG PLACEME...

Страница 4: ...tive that the control compartments burners and circulating blower and its passageway in the appliance and venting system are kept clean The appliance and its venting system should be inspected before...

Страница 5: ...h the appliance is to be installed is HEIGHT 14 5 WIDTH 25 DEPTH 11 The minimum allowable chimney flue size is 6 round 2 2 MINIMUM OPENING 44 7 8 36 1 2 4 SIDED BACKER PLATE ALUMINUM TRIM 36 15 1 2 25...

Страница 6: ...n where the vent will pass through the house without cutting a floor or roof joist If the appliance is installed directly on carpeting vinyl tile or other combustible material other than wood flooring...

Страница 7: ...er Column When the appliance is installed at elevations above 4 500ft and in the absence of specific recommendations from the local authority having jurisdiction the certified high altitude input rati...

Страница 8: ...IL AUCUN MATERIAU DEVANT ENTRER EN CONTACT AVEC LES FLAMMES AUTRE QUE CELUI QUI EST FOURNI AVEC CET APPAREIL PAR LE FABRICANT ELECTRICAL RATING CLASS 115V 1 5AMP 60HZ THE APPLIANCE MUST BE VENTED USIN...

Страница 9: ...NON COMBUSTIBLE STRAPPING TO MAINTAIN THE REQUIRED CLEARANCE FROM COMBUSTIBLES USE WOLF STEEL LTD SUPPORT RING ASSEMBLY W010 0370 OR EQUIVALENT NON COMBUSTIBLE STRAPPING TO MAINTAIN THE MINIMUM CLEARA...

Страница 10: ...chimney with screws and plugs not supplied C INSIDE Attach and secure the flex liners to the vent connection assembly using the same procedure as before ensuring that the marked exhaust liner is attac...

Страница 11: ...use open flame WARNING RISK OF FIRE EXPLOSION OR ASPHYXIATION ENSURE THERE ARE NO IGNITION SOURCES SUCH AS SPARKS OR OPEN FLAMES SUPPORT GAS CONTROL WHEN ATTACHING GAS SUPPLY PIPE TO PREVENT DAMAGING...

Страница 12: ...ANY NON COMBUSTIBLE MATERIALS SUCH AS BRICK MARBLE GRANITE ETC PROVIDED THAT THESE MATERIALS DO NOT GO BELOW THE SPECIFIED DIMENSION AS ILLUSTRATED DO NOT STRIKE SLAM OR SCRATCH GLASS DO NOT OPERATE A...

Страница 13: ...ERIALS MUST NOT INTERFERE WITH AIR FLOW THROUGH AIR OPENINGS LOUVRES OPENINGS OPERATION OF LOUVRES OR DOORS OR ACCESS FOR SERVICE OBSERVE ALL CLEARANCES WHEN APPLYING COMBUSTIBLE MATERIALS BEFORE DOOR...

Страница 14: ...heat activated curing process A Place the rear log 1 onto the two log supports and against the air intake pipe B Position logs 2 and 3 against the grate posts and line up the studs located on the burn...

Страница 15: ...cluded with each kit If this appliance is being installed into an existing wood burning zero clearance fireplace then be aware of this precaution Any circulation air opening may be covered with noncom...

Страница 16: ...ERATION FOR YOURSAFETY READBEFOREOPERATING POUR VOTRE SECURITE LIRE AVANT DE FAIRE FONCTIONNER WARNING IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY D...

Страница 17: ...ADINGS TIGHTEN SCREWS FIRMLY TO SEAL DO NOT OVER TORQUE LEAK TEST 39 6 PILOT BURNER THERMOCOUPLE THERMOPILE P I L O T PILOT SCREW A B 6 2 VENTURI ADJUSTMENT This appliance has an air shutter that has...

Страница 18: ...FLAME MUST ENVELOPE UPPER 3 8 TO 1 2 OF THERMOCOUPLE THERMOPILE 6 3 FLAME CHARACTERISTICS 6 4 RESTRICTING VERTICAL VENTS Some vent configurations may display a very active flame If this appearance is...

Страница 19: ...nd bottom of the door is not broken or missing Replace if necessary 8 If for any reason the vent air intake system is disassembled re install and re seal per the instructions provided for the initial...

Страница 20: ...the gasket holding the glass in place Careful not to break the glass GLASS GASKET DOOR FRAME GLASS RETAINER WARNING DO NOT USE SUBSTITUTE MATERIALS GLASS MAY BE HOT DO NOT TOUCH GLASS UNTIL COOLED CAR...

Страница 21: ...k on Because the blower is thermally activated when turned on it will automatically start approximately 5 15 minutes after lighting the appliance and will run for approximately 30 45 minutes after the...

Страница 22: ...T IS AN INTEGRAL SAFETY COMPONENT REPLACE ONLY WITH A FAST ACTING THERMOCOUPLE SUPPLIED BY WOLF STEEL LTD WARNING 8 0 REPLACEMENTS COMPONENTS REF NO PART NO DESCRIPTION 1 W725 0039 NATURAL GAS VALVE 1...

Страница 23: ...ON OFF REMOTE 33 F52 THERMOSTATIC REMOTE 34 GD 660 REMOTE WALL SWITCH WITH 20 WIRE 35 GI823KT DECORATIVE BRICK PANELS 36 W175 0162 CONVERSION KIT NG LP 36 W175 0192 CONVERSION KIT LP NG 37 GIZBP6 3 3...

Страница 24: ...24 W415 0224 G 02 28 11 7 6 16 5 27 28 21 35 41 1 24 2 14 10 11 12 13 47 45 38 40 41 3...

Страница 25: ...burning no gas to main burner gas knob is on HI wall switch thermostat is on Thermostat or switch is defective Connect a jumper wire across the wall switch terminals if main burner lights replace swi...

Страница 26: ...ames are very aggressive Door is ajar Ensure the mechanical means of securing the door is providing a tight seal Carbon is being deposited on glass logs or combustion chamber surfaces Air shutter has...

Страница 27: ...ftops buildings nearby trees hills mountains inadequate vents or ventilation excessive venting configurations insufficient makeup air or negative air pressures which may or may not be caused by mechan...

Страница 28: ...28 W415 0224 G 02 28 11 11 0 SERVICE HISTORY 43 1...

Отзывы: