HORIZONTAL TERMINATION
EN
(H
T
) < (V
T
)
Simple venting configuration (only one 45° and 90° elbow)
40 (12.2)
39 (11.9)
See graph to determine the required vertical
rise
V
T
for the required horizontal run
H
T
.
REQUIRED
VERTICAL
RISE IN FEET
(METERS)
V
T
30 (9.1)
20 (6.1)
10 (3.1)
0
2.5
(0.8)
5
(1.5)
7.5
(2.3)
10
(3.1)
12.5
(3.8)
15
(4.6)
17.5
(5.3)
20
(6.1)
HORIZONTAL VENT RUN PLUS OFFSET IN
FEET (METERS)
H
T
The shaded area within the lines represents
acceptable values for
H
T
and
V
T
For vent configurations requiring more than one 45° elbow and 90° elbow, the following formulas
apply:
Formula 1: H
T
< V
T
Formula 2: H
T
+ V
T
< 40 feet (12.2m)
Example:
V
1
= 8 FT (2.4m)
V
T
=
V
1
= 8 FT (2.4m)
H
1
= 2.5 FT (0.8m)
H
2
= 2 FT (0.6m)
H
R
=
H
1
+
H
2
= 2.5 FT (0.8m) + 2 FT (0.6m) = 4.5 FT (1.4m)
H
O
= .03 (one 45° elbow + two 90° elbows - 135°) = .03 (225 - 135°) = 2.7 FT (0.8m)
90°
H
T
=
H
R
+
H
O
= 4.5 FT (1.4m) + 2.7 FT (0.8m) = 7.2 FT (2.2m)
45°
H
H
T
+
V
T
= 7.2 FT (2.2m) + 8 FT (2.4m) = 15.2 FT (4.6m)
1
90°
Formula 1:
H
T
< V
T
7.2 FT (2.2m) < 8 FT (2.4m)
Formula 2:
H
T
+ V
T
< 40 FT (12.2m)
15.2 FT (4.6m) < 40 FT (12.2m)
Since both formulas are met, this vent configuration is acceptable.
16.5A
V
1
H
2