17
W415-0672 / C / 08.13.12
3.9 VERTICAL
TERMINATION
Simple venting configurations.
See graph to determine the required vertical rise
V
T
for the
required horizontal run
H
T
.
REQUIRED
VERTICAL
RISE IN
FEET
V
T
HORIZONTAL VENT RUN PLUS OFFSET IN FEET
H
T
For vent configurations requiring more than one 90° elbow, the following formulas apply:
Formula 1: H
T
< V
T
Formula 2: H
T
+ V
T
< 40 feet
Example:
V
1
= 5 FT
V
2
= 10 FT
V
T
=
V
1
+ V
2
= 5 + 10 = 15 FT
H
1
= 3 FT
H
2
= 2.5 FT
H
R
=
H
1
+ H
2
= 3 + 2.5 = 5.5 FT
H
O
= .03 (three 90° elbows - 90°)
= .03 (270° - 90°) = 5.4 FT
H
T
=
H
R
+ H
O
= 5.5 + 5.4 = 10.9 FT
H
T
+ V
T
= 10.9 + 15 = 25.9 FT
Formula 1:
H
T
< V
T
10.9 < 15
Formula 2:
H
T
+ V
T
< 40 FT
25.9 < 40
Since both formulas are met, this vent configuration is acceptable.
The shaded area within the lines represents acceptable
values for
H
T
and
V
T
0
5
10
15
20
40
10
20
30
3
(H
T
) < (V
T
)
18.6
V
2
H
2
V
1
H
1
90°
90°
90°
Содержание BCDV33NR
Страница 51: ...51 W415 0672 C 08 13 12 14 0 SERVICE HISTORY 43 1 ...
Страница 52: ...52 W415 0672 C 08 13 12 ...