background image

26

W415-0680 / 04.10.08

FRAMING

HORIZONTAL VENT SECTIONS:

 - 

A minimum clearance of 1" at the bottom and sides of the vent and 2" at the top on 

all horizontal runs to combustibles is required. Use fi restop spacer W010-1774 (supplied). 

VERTICAL VENT SECTIONS:

 - 

A minimum of 1" all around the vent pipe on all vertical runs to combustibles is required 

except for clearances in fi replace  enclosures**. See 

"MINIMUM ENCLOSURE CLEARANCES"

 section. Use fi restop 

spacer W500-0096 (not supplied).

MINIMUM CLEARANCE TO COMBUSTIBLE CONSTRUCTION FROM FIREPLACE AND VENT 
SURFACES:

Non-Combustible framing:
Top   

  

         

           

 

0" to stand-offs if using optional clean face surround

Combustible framing:
Sides, back, and bottom of the unit         

0" to stand-offs*

Top   

 

 

           

 

3 1/2" to stand-offs if using optional clean face surround

Non-combustible fi nishing:
Top   

 

 

       

 

6 1/2" if using optional clean face surround

Combustible fi replace fi nishing:
Sides, bottom and top          

           

0" to fi replace edge

Enclosure top 

 

           

 

8 1/4" to top of fi replace

Recessed depth   

           

 

17 1/4"

Sides and bottom of the vent pipe           

1"

Top of vent pipe   

           

 

2"

Ceiling      

   

           

 

72" from bottom of unit

BCDV36CF(G)

* See alternate clearances on page 28 if using optional clean face surround.
** Vertical vent sections in fi replace enclosures require a minimum of 1 1/2" all around the vent pipe.

MINIMUM CLEARANCE TO COMBUSTIBLE CONSTRUCTION FROM FIREPLACE AND VENT 
SURFACES:

Combustible framing:
Sides, back and bottom of the unit       

0" to stand-offs

Top 

 

    3 

1/2" 

to 

stand-offs

Non-combustible fi nishing:
Top   

 

 

               

6 1/2" to fi replace edge

Combustible fi replace fi nishing:
Sides and bottom 

 

              0" to fi replace edge

Enclosure top 

 

               

13 1/2" to top of fi replace

Recessed depth   

               

25"

Top, sides and bottom of vent pipe               2"
Ceiling   

 

 

 

72" from bottom of unit

BCDV42CF

HORIZONTAL VENT SECTIONS:

 A minimum clearance of 2" all around the vent pipe on all horizontal runs to combus-

tibles is required. Use fi restop spacer W010-1778 (supplied).

VERTICAL VENT SECTIONS:

 A minimum of 1" all around the vent pipe on all vertical runs to combustibles is required. 

Use fi restop spacer W500-0028 (not supplied).

 

Содержание BCDV2CFN

Страница 1: ...1 W415 0680 04 10 08 10 00 W415 0680 04 10 08...

Страница 2: ...arances Optional Clean Face Surround Installation BCDV36CF G only Finished Floor Installation Hearth Installation NOTE CHANGES OTHER THAN EDITORIAL ARE DENOTED BY A VERTICAL LINE IN THE TABLE OF CONTE...

Страница 3: ...President s Limited Lifetime Warranty WOLF STEEL LTD may at its discretion fully discharge all obligations with respect to this warranty by refunding to the original warranted purchaser the wholesale...

Страница 4: ...tions with BCDV36CF G are common to both the BCDV36CF and the BCDV36CFG FOR YOUR SATISFACTION THIS FIREPLACE HAS BEEN TEST FIRED TO ASSURE ITS OPERATION AND QUALITY BCDV36CF G Maximum input for the BC...

Страница 5: ...AL INLET LEFT SIDE 41 1 2 37 35 1 2 GAS INLET FIGURE 5 INSTALLATION OVERVIEW FIGURE 7 See the section MINIMUM MANTEL AND ENCLOSURE CLEARANCES Side Wall See the section INSTALLATION FRAMING See the sec...

Страница 6: ...htemperaturesilicone RTV This same sealant may be used on both the inner exhaust and outer intake vent pipe joints of all other approved vent systems except for the exhaust vent pipe connection to the...

Страница 7: ...7 W415 0680 04 10 08 FIGURE 8...

Страница 8: ...For optimum performance it is recommended that all horizontal runs have a 1 rise per foot When terminating vertically the vertical rise is a minimum 3 feet and a maximum 40 feet from the centre of th...

Страница 9: ...he 45 offset In this case zero rise is acceptable when using rigid See FIGURE 18 Flexible venting must maintain a 6 rise See FIGURE 19 PERISCOPE TERMINATION CORNER TERMINATION BCDV36CF G BCDV42CF PERI...

Страница 10: ...n Horizon tal run vertical rise to maximum of 40 feet Horizontal run verti cal rise to maximum of 24 75 feet 4 2 times the verti cal rise equal to or greater than the horizontal run Vertical rise is e...

Страница 11: ...ET HT The shaded area within the lines represents acceptable values for HT and VT for the following symbols used in the venting calculations and examples are greater than equal to or greater than less...

Страница 12: ...TICAL RISE IN INCHES VT HORIZONTAL VENT RUN PLUS OFFSET IN FEET HT The shaded area within the lines represents acceptable values for HT and VT when HT VT Simple venting con guration only one 90 elbow...

Страница 13: ...9 ft V2 6 ft VT V1 V2 9 6 15 ft H1 3 ft H2 2 ft H3 1 5 ft HR H1 H2 H3 3 2 1 5 6 5 ft HO 03 four 90 elbows 90 03 90 90 90 90 90 8 1 ft HT HR HO 6 5 8 1 14 6 ft HT VT 14 6 15 29 6 ft Formula 1 HT VT 14...

Страница 14: ...19 25 Since both formulas are met this vent con guration is acceptable For vent con gurations requiring more than two 90 elbows the following formulas apply H1 H2 H3 H4 V1 V2 90 90 45 90 90 FIGURE 28...

Страница 15: ...g con guration only two 90 elbows FIGURE 29 V1 5 ft V2 10 ft VT V1 V2 5 10 15 ft H1 3 ft H2 2 5 ft HR H1 H2 3 2 5 5 5 ft HO 03 three 90 elbows 90 03 90 90 90 90 5 4 ft HT HR HO 5 5 5 4 10 9 ft HT VT 1...

Страница 16: ...this vent con guration is unacceptable H1 H2 V3 V1 90 90 90 V2 90 when HT VT Simple venting con gurations See graph to determine the required vertical rise VT for the required horizontal run HT FIGURE...

Страница 17: ...Example 1 45 90 H1 H2 V1 FIGURE 35 V1 8 ft VT V1 8 ft H1 2 5 ft H2 2 ft HR H1 H2 2 5 2 4 5 ft HO 03 one 45 elbows two 90 elbows 135 03 225 135 2 7 ft HT HR HO 4 5 2 7 7 2 ft HT VT 7 2 8 15 2 ft Formul...

Страница 18: ...ing con gurations 45 MAXIMUM VERTICAL RISE IN FEET VT HORIZONTAL VENT RUN PLUS OFFSET IN FEET HT The shaded area within the lines represents acceptable values for HT and VT For vent con gurations requ...

Страница 19: ...ow three 90 elbows 135 03 45 90 90 90 135 5 4 ft HT HR HO 8 5 4 13 4 ft HT VT 13 4 2 5 15 9 ft Formula 1 HT VT 3VT 3 x 2 5 7 5 ft 13 4 7 5 Since this formula is not met this vent con guration is unacc...

Страница 20: ...unit Press rmly on the cap while securing to ensure an airtight seal Do not damage the gasket FAILURE TO INSTALL THE CAP WILL CAUSE THE FIREPLACE TO FUNCTION IMPROP ERLY AND CAN CAUSE INJURY OR PROPER...

Страница 21: ...f 2 all around the vent pipe on all horizontal runs to combustibles is required Use restop spacer W010 1778 supplied VERTICAL VENT SECTIONS A minimum of 1 all around the vent pipe on all vertical runs...

Страница 22: ...p only on the 7 outer vent pipe ELBOW SPACER For safe and proper operation of the replace follow the venting instructions exactly All inner exhaust and outer intake vent pipe joints may be sealed usin...

Страница 23: ...lustrated The vent system must be supported approximately every 3 feet for both vertical and horizontal runs Use noncombustible strapping to maintain a clearance to combustibles of 1 VERTICAL AIR TERM...

Страница 24: ...eelventpipecollar orequivalentloosely onto the air terminal assembly as it is passed through the attic The air terminal must be located vertically and plumb 6 Remove nails from the shingles above and...

Страница 25: ...2 strand solid core millivolt wire through the electrical hole located at the bottom left side of the unit The recommended maximum lead length depends on wire size WIRE SIZE MAX LENGTH 14 gauge 100 f...

Страница 26: ...replace edge Enclosure top 8 1 4 to top of replace Recessed depth 17 1 4 Sides and bottom of the vent pipe 1 Top of vent pipe 2 Ceiling 72 from bottom of unit BCDV36CF G See alternate clearances on p...

Страница 27: ...ensure that clearance to combustibles is maintained within the cavity Combustible materials may be installed ush with the front of the replace but must not cover any of the black face areas of the rep...

Страница 28: ...TLE THIS AREA MUST REMAIN EXPOSED TO ALLOW FOR PROPER DOOR REMOVAL 12 TO COMBUSTIBLE MANTLE The finishing material can be installed below the top opening a maximum of 1 1 2 Enough clearance to the doo...

Страница 29: ...1 2 of cement board and steel header supplied with surround kit or non combustible equiva lent must be used on the top only of the front face See Figure 80 See Venting Section FIGURE 79 FIGURE 81 NOTE...

Страница 30: ...er installing to a nished oor or a hearth a 3 8 clearance must be maintained at the bottom of the clean face surround kit To obtain this clearance a replace riser is required When installing to a nish...

Страница 31: ...ind the top lip of the replace front opening FIGURE 90 and secure using the screws provided through the slot in the surround clip and into the pre drilled hole in the clean face surround FIGURE 90 If...

Страница 32: ...RE 97 FIGURE 97 FIGURE 98 FIGURE 98 2 Move the two small logs 2 3 into position lining up the studs located on the burner with the holes on the bottom of the logs Ensure that the small logs sit at on...

Страница 33: ...the door frame face down careful not to scratch the paint 2 Center the gasketed glass inside the door frame with the thick side of the gasket facing up 3 Bend the glass retainers located along the ed...

Страница 34: ...ayed ignition PHAZER logs glow when exposed to direct ame 4 Place the bottom of the left crossover log 4 onto the stud on the left side of the log support The top of the log should rest in the pocket...

Страница 35: ...of tray FIGURE 110 NOTE The distribution of clear glass embers over the burner tube will in uence the ame height FIGURE 109 BULB REPLACEMENT 1 Remove the glass and glass ember tray 2 Remove the burner...

Страница 36: ...er assembly to the side 6 Reverse procedure to re assemble SPACERS FIGURE 114 FIGURE 114 FIGURE 115 FIGURE 115 FIGURE 116 FIGURE 117 INSTALLING THE BLOWER INSTALLATIONTOBEDONEBYAQUALIFIEDINSTALLERandm...

Страница 37: ...inutes after the replace has been lit and for approximately 30 45 minutes after the replace has been turned off Use of the fan increases the output of heat Unplug the power cord from the receptacle Co...

Страница 38: ...ed route 2 strand solid core wire through the electrical hole located at the bottom left side of the unit FIGURE 125 BATTERY HOLDER GAS VALVE PILOT ASSEMBLY IGNITION MODULE PILOT GAS LINE Orange I thr...

Страница 39: ...commended maximum lead length depends on wire size WIRE SIZE MAX LENGTH 14 gauge 100 feet 16 gauge 60 feet 18 gauge 40 feet A 20 length of millivolt wire is connected to the terminal block for the lig...

Страница 40: ...ple has cooled Allow ap proximately 60 seconds for the thermocouple to cool When lighting and re lighting the gas knob cannot be turned from pilot to off unless the knob is depressed slightly 1 Stop R...

Страница 41: ...T TRY TO LIGHT ANY APPLIANCE DO NOT TOUCH ANY ELECTRIC SWITCH DO NOT USE ANY PHONE IN YOUR BUILDING IMMEDIATELY CALL YOUR GAS SUPPLIER FROM A NEIGHBOUR S PHONE FOLLOW THE GAS SUPPLIER S INSTRUCTIONS I...

Страница 42: ...before lifting glass ember tray out When replacing burner absolutely no glass can be in cup sur rounding the ori ce HINT If glass falls into cup and surrounds the ori ce insert a clean bag into a vacu...

Страница 43: ...a service person FIGURE 136 FLAME ADJUSTMENT It is important to periodically perform a visual check of the pilot and the burner ames Compare them to the gures shown If any ames appear abnormal call a...

Страница 44: ...0538 FLUE CAP c w GASKET 34 W010 0764 PAN BURNER 35 GL 639 LOG SET 36 W135 0183 BACK LOG 1 37 W135 0184 LEFT MIDDLE LOG 2 38 W135 0185 RIGHT MIDDLE LOG 3 39 W135 0186 LEFT CROSSOVER LOG 4 40 W135 0187...

Страница 45: ...12 8 FLEXIBLE VENT PIPE 5 5 FT GD430 10 FT 105 W730 0011 5 FLEXIBLE VENT PIPE 11 5 FT 106 W730 0013 8 FLEXIBLE VENT PIPE 11 5 FT C W SPACERS 107 W010 0810 WALL SUPPORT ASSEMBLY BCDV42CF TERMINAL KITS...

Страница 46: ...46 W415 0680 04 10 08...

Страница 47: ...pen Verify that the inlet pressure reading is within acceptable limits inlet pressures must not exceed 14 W C Module is not grounded Verify the value and pilot assemblies are properly grounded to the...

Страница 48: ...hermopile Turn up pilot ame Replace pilot assembly Thermopile shorting Clean thermopile connection to the valve Reconnect Replace thermopile valve Remote wall switch wire is too long too much resistan...

Страница 49: ...mes are very aggressive Door is ajar Tighten screws holding door in place MODEL BCDV42CF ONLY Aggressive venting action due to vent height Restrict vent exit See RESTRICTING VERTICAL VENTS VENT HEIGHT...

Страница 50: ...50 W415 0680 04 10 08 Wolf Steel Fireplace Service History This fireplace must be serviced annually depending on usage Date Service Technician Name Service Performed Special Concerns Dealer Name...

Страница 51: ...51 W415 0680 04 10 08 NOTES...

Страница 52: ...52 W415 0680 04 10 08 NOTES...

Отзывы: