CONTINENTAL CONTROL SYSTEMS WattNode BACnet Series Скачать руководство пользователя страница 3

3

The meter only draws 10-30 milliamps, so the rating of any switches, discon-
nects, fuses, and/or circuit breakers is determined by the wire gauge, the mains 
voltage, and the current interrupting rating required.

 

The switch, disconnect, or circuit breaker must be as close as practicable 
to the meter and must be easy to operate.

 

Use circuit breakers or fuses rated for 20 amps or less.

 

Use ganged circuit breakers when monitoring more than one line voltage.

 

The circuit breakers or fuses must protect the mains terminals labeled 

Ø

A

Ø

B

, and 

Ø

C

. If neutral is also protected, then the overcurrent protec-

tion device must interrupt both neutral and the ungrounded conductors 
simultaneously.

 

The circuit protection / disconnect system must meet IEC 60947-1 and IEC 
60947-3, as well as all national and local electrical codes.

3.3.2  Line Wiring

● 

Always disconnect power

 before connecting the line voltage inputs to 

the meter.

● 

For the line voltage wires, CCS recommends 16 to 12 AWG stranded wire, 
type THHN, MTW, or THWN, 600 V.

 

Do not place more than one voltage wire in a screw terminal; use separate 
wire nuts or terminal blocks if needed.

● 

Verify that the line voltages match the line-to-line 

Ø-Ø

 and line-to-neutral 

Ø-

N

 values printed in the white box on the front label.

Connect each line voltage to the appropriate phase; also connect ground and 
neutral (if applicable). The neutral connection “

N

“ is not required on delta mod-

els (3D-240, 3D-400, and 3D-480), but we recommend connecting it to ground 
if neutral is not present.

The screw terminals handle wire up to 12 AWG. Connect each voltage line to 
the green terminal block as shown in 

Figure 1

 above. After the voltage lines 

have been connected, make sure both terminal blocks are fully seated in the 
meter.

When power is first applied, check that the LEDs behave normally: on models 
with status LEDs, if you see them flashing red-green-red-green (see 

Figure 7

), 

the line voltage is too high for this model, so disconnect the power immediately!

3.3.3  Grounding

The WattNode uses a plastic enclosure, insulation, and internal isolation bar-
riers instead of protective earthing. The ground terminal on the green screw 
terminal block is a functional ground, designed to improve the measurement 
accuracy and noise immunity. If necessary, this terminal may be left discon-
nected on wye models (

-

3Y

).

3.4  Connect Current Transformers

To meet the UL listing requirements, the WattNode meter may only be used with 
these UL listed or recognized current transformer models. These all generate 
333.33 millivolts AC at rated current. See the current transformer datasheets 
for CT ratings.

ACT-0750-

xxx 

CTL-1250-

xxx 

CTM-0360-

xxx 

CTS-0750-

xxx 

CTS-1250-

xxx

 CTS-2000-

xxxx 

CTB-

www

X

hhh

-

xxxx 

CTBL-

www

X

hhh

-

xxxx 

CTT-0300-

xxx 

CTT-0500-

xxx

 CTT-0750-

xxx

 CTT-1000-

xxx

 

CTT-1250-

xxx

 

xxx

” indicates the full scale current rating.

 

www

” and “

hhh

” indicate the width and height in inches.

 

dddd

” indicates the opening diameter of the loop for flexible Rogowski 

CTs.

See the web article 

Selecting Current Transformers

 for information on se-

lecting appropriate current transformers (CTs).

 

Do not

 use ratio or current output CTs such as 1 amp or 5 amp output 

models! 

 

See the CT datasheets for the maximum input current ratings.

 

Be careful to match the CTs with the voltage phases. Make sure the 

Ø

A CT

 

is measuring the current on the same phase being monitored by 

Ø

A

, and 

the same for phases B and C. Use the supplied colored labels or colored 
tape to identify the CT leads.

 

To minimize current measurement noise, avoid extending the CT wires, 
especially in noisy environments. If it is necessary to extend the wires, use 
twisted pair wire 22 to 14 AWG, rated for 300 V or 600 V (not less than the 
service voltage) and shielded if possible.

 

Find the source arrow or label “THIS SIDE TOWARD SOURCE” on the CT 
and face/point toward the source of current.

 

OPTIONAL: if you see spurious readings on unused phases, jumper the 
unused CT inputs: for each unused CT, connect a short wire from the 
terminal marked with a white dot to the terminal marked with a black dot.

To install the CTs, pass the conductor to be measured through the CT and con-
nect the CT leads to the meter. 

Always remove power before disconnecting 

any live conductors. 

Put the line conductors through the CTs as shown in 

Figure 1

 above.

CTs are directional. If they are mounted backwards or with their white and black 
wires swapped the measured power will be negative. The status LEDs indicate 
negative measured power by flashing red.

Split-core CTs can be opened for installation around a conductor. A nylon cable 
tie may be secured around the CT to prevent inadvertent opening. 

3.4.1  CT Wiring

Connect the white and black CT wires to the meter terminals marked 

Ø

A CT

Ø

B CT

 , and 

Ø

C CT

 (see 

Figure 1

 above). Excess length may be trimmed from 

the wires if desired. The current transformers connect to the six position black 
screw terminal block. Connect each CT with the white wire aligned with the 
white dot on the label, and the black wire aligned with the black dot. Note the 
order in which the phases are connected, as the line voltage phases 

must

 

match the current phases for accurate power measurement.

3.5  Connect the Output Signals

 

The meter outputs are isolated from dangerous voltages, so you can con-
nect them at any time.

 

If the output wiring is near line voltage wiring, use wires or cables with a 
300 V or 600 V rating (not less than the service voltage).

 

If the output wiring is near bare conductors, it should be double insulated 
or jacketed.

 

You may install two wires into each screw terminal by twisting the wires to-
gether, inserting them into terminal, and securely tightening. Note: a loose 
wire can disable an entire network section. 

 

Use twisted-pair cable (unshielded or shielded) to prevent interference.

3.5.1  BACnet MS/TP

The WattNode BACnet meter can be connected to BACnet monitoring equip-
ment, gateways, and other BACnet devices.

Use DIP switches 1-6 to select the BACnet MAC address (0 to 63).

DIP Switch

1

2

3

4

5

6

Up

 (1) Value

1

2

4

8

16

32

Address

Examples

1

1, Up

0, Down 0, Down 0, Down 0, Down 0, Down

1+2+4 = 7

1, Up

1, Up

1, Up

0, Down 0, Down 0, Down

4+16 = 20

0, Down 0, Down

1, Up

0, Down

1, Up

0, Down

1+2+16+32 = 51

1, Up

1, Up

0, Down 0, Down

1, Up

1, Up

Select the baud rate by setting DIP switch positions 7 and 8 as shown below. 
The change will take effect in approximately ten seconds.

Baud Rate

DIP Switch 7

DIP Switch 8

9,600 (default)

0, Down

0, Down

19,200

1, Up

0, Down

38,400

0, Down

1, Up

76,800

1, Up

1, Up

3.5.2  Connect RS-485

X

C

B+

A-

W

ATT

N

ODE

W

ATT

N

ODE

A- B+ C

RS-485

X

C

B+

A-

Отзывы: