
UM-15093000-AA1
Page
24
Object name
Type &
Instance
Readable/
Writable
Description
Range and Definition
Lock
AV 18
RW
LOCK
Bit Definition:
0
: MODE button
(dec=1)
1
: Down button
(dec=2)
2
: Up button
(dec=4)
3
: FAN SPEED button
(dec=8)
4
: Power On/Off button
(dec=16)
5
: SET (or
℃
/
℉
) button
(dec=32)
6
: ESI contact
detection
(dec=64)
7
: Door/Window
contact detection
(dec=128)
8
: Modification for
communication
parameters
(dec=256)
i.e. baud rate, MAC addr,
device inst.
9
: Control DOs by
thermostat algorithm
(0) or BACnet sup. (1)
(dec=512)
10~15
: reserved/unused
Bit Value
0: Unlock / enable
1: Lock / disable
Examples (add dec values to
lock multiples) For more details
see Lock Function Setup and
Examples section of this manual
Control Out
Percentage
AV 19
R/W
Percentage of Modulating/
Floating Control Output
0
~
100 (0%
~
100%)
MAC Address
AV 19
R/W
MAC Address
0~127
Device Instance
AV 21
R/W
Device Instance
0~4194302
(Note: Before changing this
value unlock modification for
communication parameters
i.e. AV17=0~255 or
512~768. Please refer to
LOCK(AV17) for details)
Humidity Offset
AV 22
R/W
Humidity Offset Value (
CH
models only
)
-300~300 (-30.0
~
30.0
%RH)