UM-15090000-AA8
Page
30
Object name
Type &
Instance
Readable/
Writable
Description
Range and Definition
Cooling Short Cycle
AV 23
R/W
Cooling Short Cycle Delay
1~3 Minutes
Cooling Maximum
Cycles
per Hour
AV 24
R/W
Cooling Maximum Cycles
per Hour
2~6 Cycles
Heating Short Cycle
AV 25
R/W
Heating Short Cycle Delay
0~3 Minutes
Heating
Maximum Cycles
per Hour
AV 26
R/W
Heating Maximum Cycles
per Hour
2~8 Cycles
Minimum Output for
AO2
AV 27
R/W
Minimum Output Voltage in
Digital Value When Reach
Low Limit for AO2
0~125 (LSB)
Span Offset for
AO2
AV 28
R/W
Span Offset for AO2
-55~0 (LSB)
CO2 Input Low
Value
AV 29
R/W
CO2 Input Low Value
0~1000 ppm
CO2 Input High
Value
AV 30
R/W
CO2 Input High Value
1000~3000 ppm
CO2 Control Output
Proportional Band
AV 31
R/W
CO2 Control Output
Proportional Band
100~2000 ppm
CO2 Setpoint
AV 32
R/W
CO2 Setpoint
600~1000 ppm
CO2 Control
Minimum Output
AV 33
R/W
CO2 Control Minimum
Output Percentage
0~20%
After Hour Extension
Time
AV 34
R/W
After Hour Extension Run
Time
5~20(0.5~2.0) Hour
Input Low Value of
Valve Feedback
AV 35
R/W
Input Low Value of Control
Valve Feedback
0~1000 (0.0
~
100.0 %)
Input High Value of
Valve Feedback
AV 36
R/W
Input High Value of Control
Valve Feedback
0~1000 (0.0
~
100.0 %)
Analog Input Low
Value
AV 37
R/W
Analog Input Low Value
0~1000 (0.0
~
100.0 %)
Analog Input High
Value
AV 38
R/W
Analog Input High Value
0~1000 (0.0
~
100.0 %)
Humidity Input Low
Value
AV 39
R/W
Humidity Input Low Value
0~1000 (0.0
~
100.0
%RH)
Object name
Type &
Instance
Readable/
Writable
Description
Range and Definition
Humidity Input High
Value
AV 40
R/W
Humidity Input High Value
0~1000 (0.0
~
100.0
%RH)
Minimum Fan
Output
AV 41
R/W
Minimum Fan Output at Auto
Fan Mode (for Modulating
Fan Application)
0%~Reg 51
Maximum Fan
Output
AV 42
R/W
Maximum Fan Output at
Auto Fan Mode (for
Modulating Fan Application)
Reg 50~100%
Low Fan Speed
Setting
AV 43
R/W
Low Fan Speed Setting (for
Modulating Fan Application)
0%~Reg 53
Содержание BASstat BAST-221C-B2