Reset Switch 

MS/TP Physical Layer Connection Options 

Web Page Configuration 

The BASrouter is configured using a web server accessible from any PC on the local network with recent versions of any standard web browser installed. To configure the 
router initially, connect it to your Windows PC using an Ethernet cable and set the PC’s IP and subnet mask in Local Area Connection –> Properties. In the Internet Protocol 
Version 4 (TCP/IPv4) settings of your Windows PC, specify an IP address and a Subnet mask in the same subnet as the BASrouter (e.g. 192.168.92.5 /24). 

 

BASrouter’s factory-programmed: Default IP address is 192.168.92.68 and a Class C subnet mask of 255.255.255.0 (/24). User Name is: admin and Password is: admin

 

ATTENTION: The default login credentials must be changed before the BASrouter system configuration can be altered. Please change the 
password to an 8-10 character alphanumeric value (at least one letter and one number). This ensures authorized access to the router only. 

 

Reset IP 

switch is located on the side of the unit.

 

Press and hold the 

Reset IP

 button using a paper clip for at least 3 seconds 

while the router is powered by USB cable. Remove USB power cable and then restore power again to complete the reset IP,  
User ID, and Password procedure to factory-programmed defaults. 
 

 
For complete datasheet and details on BASrouter, support, or compliance information, please download our BASrouter User Manual at: 

https://www.ccontrols.com/basautomation/basportable.php

 

and click on the Support tab under More Information.

  

Contemporary Control Systems, Inc. reserves the right to make changes in the specifications of the product described within this manual at any time without notice and without obligation of Contemporary Control Systems, Inc.  
to notify any person of such revision or change. 

 

2-wire MS/TP Bus  

 

 

 

 

3-wire MS/TP Bus 

 

 

TD070210-0IL 

Connect shield to earth at only one point 

Connect shield to earth at only one point 

Do 

NOT

 connect 

shield to SC pin 

!

 

Do 

NOT

 connect 

shield to SC pin 

!

 

Up to 31 Full-load 

MS/TP 

Field Devices 

BASRTP-B 

BASRTP-B 

120 Ω

 

120 Ω

 

120 Ω

 

120 Ω

 

(optional) 

(optional) 

Up to 31 Full-load 

MS/TP 

Field Devices 