Installation Environment Requirements
Table 2.2. Installation Environment Requirements
Item Specification
Ambient specifications
Operating temperature
0 - 50ºC
Storage temperature
-10 - 60ºC
Operating Humidity
20 - 85%RH(no condensation)
Floating dust particles
Not to be excessive
Corrosive gases
None
Line noise
AC line: 2kV (Using the AC adapter IPC-ACAP12-01)
Signal line: 1kV (EN61000-4-4 Level3, IEC1000-4-4 Level 3)
Contact discharge / 4kV (EN61000-4-2 Level 2, IEC1000-4-2 Level 2)
Line-noise
resistance
Static
electricity
resistance
Atmospheric discharge / 8kV (EN61000-4-2 Level 3, IEC1000-4-2 Level 3)
Vibration
resistance
Anti-shaking 10 - 57Hz/semi-amplitude 0.15mm
One cycle (10-150-10 Hz) of 1 oct/min test at 19.6 m/s
2
(2G) between 57 an
150 Hz x 10 times in three (X/Y/Z) directions (80 minutes each)
(JIS C0040-compliant, IEC60068-2-6-compliant)
Impact resistance
Tested with 11-ms half-sine wave at 98 m/s
2
(10G) three times in each of
three (X/Y/Z) directions
(JIS C0041-compliant, IEC60068-2-27-compliant)
Ground
Class D grounding (previous class 3 grounding)
Water-proof and dust-proof IP65, front
Power Up Specification for DC Powered Models
Time
Volt
11.4V