Contec DIO-4/4(FIT)GY Скачать руководство пользователя страница 3

 

 

Ver.1.00

 

 

DIO-4/4(FIT)GY

 

 

 

3

 

 

 

How to Connect an Interface Connector 

When connecting the Module to an external device, you can 
use the supplied connector plug.     
To wire the Module, strip the sheath about 9 - 10mm from an 
end of the wire and insert the exposed wire into an opening.  
Tighten the screw to fasten the inserted wire.  Applicable 
wires are AWG28 - 16. 

- Applicable wire:

3.81mm pitch, 12-pin type, 8.0A rated current
MC1, 5/12-GF-3.81 [made by Phoenix Contact Corp.]

- Applicable plug:

Front screw type with connector stopper flange
FRONT-MC 1,5/12-STF-3,81 [made by Phoenix Contact Corp.]
Applicable cable: AWG28-16

Turn the screw to fasten the wire.

9 - 10mm

DI-8

Device

ID

COM 0

NC

X

COM1

NC

0

3

1

2

6

5

4

7

4 5 6 7

X

0 1 2 3

0

4

0

4

6

2

5

1

3

7

 

CAUTION

 

Removing the connector plug by grasping the cable can 
break the wire. 

Signal Layout on the Interface Connector 

The Module can be connected to an external device using a 
12-pin connector that is provided on the Module face. 

COM 0 --- +/-COM
N.C.
X 0 --- IN 0
X 1 --- IN 1
X 2 --- IN 2
X 3 --- IN 3

Y 0 --- OUT 0

COM 1 --- +COM
COM 2 --- -COM

Y 1 --- OUT 1
Y 2 --- OUT 2
Y 3 --- OUT 3

Input port

plus / minus common

Output port minus common

Digital Input: 4points

Digital Output: 4points

Output port plus common

 

 

 

Input section 

Figure below shows the input equivalent circuit for the interface 
section of this product. 
The signal input section consists of an Optocoupler isolated 
input (compatible with both current sink output and current 
source output).  An external power supply is therefore 
required to drive the input section of this module.    The power 
requirement for the <DIO-4/4(FIT)GY> or <DI-8(FIT)GY> is 
about 8 mA per input channel at 24 VDC (about 4 mA at 12 
VDC). 

Input Circuit 

Vcc

3k

Ω

3k

Ω

External circuit

Module

Optocoupler

Input

pin

Input

pin

+/-

common

Input contact

point

Input contact

point

12V - 24VDC

External

power supply

Optocoupler

 

Example of a Connection to Current Sink Output 

3k

Ω

Vcc

Current sink

output

Optocoupler

Input

pin

Minus

common

12V - 24VDC

External

power supply

External circuit

Module

 

Example of a Connection to Current Source Output 

Minus

common

3k

Ω

External circuit

Module

Optocoupler

Input

pin

Current

source output

External

power supply

Vcc

 

Output section 

Figure below shows the output circuit for the interface section 
of this product.  The signal output section consists of an 
Optocoupler isolated open collector output (current sink type).   
An external power supply is therefore required to drive the 
output section of this module. 
The maximum output current rating per channel is 150 mA for 
this product (at 12 - 24 VDC) or 50mA for this product (at 36 - 
48 VDC).  A surge voltage protection circuit (zener diode) is 
provided for the output transistors of this module.    When the 
module drives relays, lamps, and other induction loads, 
however, another surge voltage countermeasure should be 
provided on the load side. 

CAUTION

 

When the power is turned on, all output will be OFF. 

Output Circuit 

Vcc

Vcc

Plus

common

Minus

common

Output

pin

Output

pin

Optocoupler

External circuit

Module

Load

Load

12V - 48VDC

External

power supply

 

Connection example: 
Using Inputs X0 

+

Input plus common (e.g., connector COM0)

Mo

du

le

 s

id

e

Input pin (e.g., connector X0)

External

power supply

12V - 24VDC

-

 

Interface Connector   

 

External I/O Circuits   

 

Отзывы: