Appendix
—
CPS- MM-LC Reference Manual (Hardware)
—
37
—
Item
CPS-MM-LC
Installation environment
Applicable pollution degree 2
*1 The patent theory of TANASHIN DENKI CO.,LTD. is applied.
*2 Use in the circuit not exceed CAT III 300V or CAT II 600 V.
*3 Value is when adjusted with standard jig
*4
Accuracy cannot be guaranteed for Isolation resistance value of 10MΩ or greater.
*5 Between voltage measurement connector and stack bus
CAUTION
You can set the modules as you desire to the configurable controller up to 16 modules.
The total current consumption of the modules should be less than 3.3A.
Function Specifications < ZCT unit >
Item
ZCT unit
Structure
Penetrating type
Rated current
100A
Rated voltage
600VAC *6
Penetrating hole diameter
φ
25mm
Isolation resistance
2200VAC
Cable length
2.9m
Connector
ZER-11V-S (or equivalent)
Physical dimensions (mm)
37.2(W)×74.5(D)×115.9(H) (No projection included)
Weight
600g
Installation method
With screws
*6 Use an isolated cable to connect through the ZCT unit.