background image

1 Calibration Instruction for Salwico ST200 and
Salwico ST600EX

Calibration Instruction

4

5103026_Salwico ST200 & Salwico ST600EX_Calibration Instruction_I0_EN_2019_C

1

Connect the suitable test-gas for the
detector, normally a 50% LEL mixture.

Recommendations:

The ST200 and ST600EX can
only respond to gas in normal
Air. This means that
Calibration gas in N2 /
Nitrogen are not suited for
these detectors.
On LNG vessels a 50% LEL
gas of CH4 Methane in air is
to be used.
For LPGs and Tankers we
normally recommend a 50%
LEL C3H8 Propane gas in air.

2

Adjust the reading to 12.0 mA using the
‘SPAN’ pot. See picture.

Figure 3. Detector ST200

Figure 4. Detector ST600EX

3

If the readout of 12.0 mA cannot be
reached even with the “SPAN” pot in the
bottom position, the sensor cell must be
replaced to a new one. Consilium
Replacement article number for ST200 and
ST600EX detectors is 004460-S.

NOTE!

When a new sensor is fitted, a
new Zero adjustment as well as
span calibration should be made.

Catalytic detectors have a
limited lifespan of up to 5
years, but can be ‘poisoned’
by silicones, salt air, very
humid air, etc. and their
output will be reduced.

1.5 Reconnecting disabled detectors

All disablements in the CGD50/500 gas detection system are presented in the
disablements list. Any enablement is made from this list.

Содержание Salwico ST200

Страница 1: ...Salwico ST200 Salwico ST600EX CGD50 500 Calibration Instruction...

Страница 2: ...ision without notice due to continued progress in methodology design and manufacturing Consilium Building Safety AB assumes no legal responsibility for any error or damage resulting from the usage of...

Страница 3: ...is instructions applies to the following products Figure 1 Salwico ST200 Part No 4470 Figure 2 Salwico ST600EX Part No 4460 NOTE It is recommended to periodically carry out a gas response check on the...

Страница 4: ...the menu tree 2 Scroll to 4 Gas Detectors and press Continue 3 Scroll to the detector that should be calibrated and press Options 4 Scroll to 3 Disable and choose Continue 5 You have to confirm the d...

Страница 5: ...ing the sensor Zero calibration Before gas Calibration is made a Zero adjustment should be made 1 Connect the multimeter to the two test points as shown in the picture 2 The multimeter readout should...

Страница 6: ...t the reading to 12 0 mA using the SPAN pot See picture Figure 3 Detector ST200 Figure 4 Detector ST600EX 3 If the readout of 12 0 mA cannot be reached even with the SPAN pot in the bottom position th...

Страница 7: ...tion for Salwico ST200 and Salwico ST600EX 5103026_Salwico ST200 Salwico ST600EX_Calibration Instruction_I0_EN_2019_C 5 1 Scroll to Menu Disablements 2 Choose the detector you just disabled and press...

Страница 8: ...logies for the marine oil and gas transport and building sectors Our commitment goes beyond the products We protect the lives of mothers and fathers sisters and brothers colleagues and friends With re...

Отзывы: