AC Input, Two-Wire Transmitter 

 
 
 
Operator’s Manual 
 
Contents: 
1.     Calibration 
2.     Connection 
3.     Mechanical 
4.     Specifications 
 
1.  Calibration Instructions 

 

 

1.1

 

The ACT-2 coarse ranging is factory set.  

         The Zero and Span potentiometers located on the   
         unit’s front panel are used for fine tuning. 
 
1.2 Calibration instrumentation: 
 
     1.    24Vdc power supply 
     2.    AC voltage/current calibrator 
     3.    High accuracy DVM 
     4.    Small screwdriver 

 
Connect the transmitter to be calibrated according to fig. #1. 

 

 
 
 
 
 
 
 
 
 
 
 
 
 

       

 

 

 
 

 
         Fig. #1 

 

 

a.    Set calibrator to 0 output 
b.    Adjust with the Zero potentiometer to obtain an output current of 4.000mA 
c.    Set the calibrator to I/V maximum. 
d.    Adjust with the Span potentiometer to obtain an output current of 20.000mA  
e.     Repeat steps a to d until satisfactory results are achieved. 
 
 
 
 
 
 
 
 
 

 