36
Operator Interface
2583701_C_EN_1812_Nortec-GS_OM
Nortec GS
BACnet Parameters Tab (continued)
The following settings appear only if
BACnet
is set to "BACnet/IP" or
"MSTP".
–
Device Name
: allows you to assign a name to the humidifier for
communications over the BACnet/IP protocol.
–
MSTP Mode:
Master or Slave
When set to BACnet MSTP the Nortec GS humidifier commu
-
nicates as a BACnet slave only. BACnet master functionality
requires installation of optional hardware.
–
Baud Rate:
Determines the speed of data transmission for
communication on the Modbus network. The higher the value,
the more its per second is transferred.
–
Device Description
: allows you to enter a description for the
humidifier.
–
Device Location
: allows you to enter the location of the
humidifier.
–
Node ID
: allows you to assign a node ID to the humidifier for
communications over the BACnet/IP protocol.
Setting range:
1-9999999
Factory setting:
1001
–
BACnet IP Port
: allows you to assign a IP port number for the
humidifier.
Setting range:
1-65535
Factory setting:
47808
–
BACnet MSTP MAC
: allows you to assign a MSTP MAC ad
-
dress for the humidifier.
Setting range:
128-254
Factory setting:
128
–
Foreign Device:
Determines the speed of data transmission.
The higher the value, the more its per second is transferred.
When Foreign Device is ON, BBMD IP Port, IP Address, and
Re-Register Time appears.