Installation As A Category III Appliance

General

1.  This venting system can be installed horizontally or 

vertically and can terminate on a rooftop or sidewall 

provided the NFGC (Nation Fuel Gas Code) and CAN/

CGA- B149 codes are followed. The venting manufacturer 

instructions must also be followed.

2.  Venting must be UL or UL/CSA listed, tested to ULC-5636 

standard. Venting may be BH, L vent or Special Gas Vent. 

The vent shall be listed and installed in accordance with 

the terms of the vent listing and the manufacturer’s 

instructions. The instructions listed below should be 

followed as well.

3.  A minimum equivalent vent length of 7 feet must be 

connected to the humidifier. Vent lengths must not 

exceed 70’ (21 m). Each 90° elbow is equivalent to 10’ 

and each 45° elbow equals 5’. The vent run should be 

as direct as possible with no more than 6 elbows in the 

system. Contact Condair technical service if you have any 

questions This category installation may not be common 

vented with any other natural draft gas appliance or 

power assist appliance.

4.  All joints must be sealed using high temperature rtv 

silicone.

5.  The gas humidifier is supplied with the following exhaust 

outlets.

a.  Nortec GS 100 3”
b.  Nortec GS 200 4”
c.  Nortec GS 300/400 5”
d.  Nortec GS 500/600 6”

6.  The venting must remain the same diameter throughout 

the installation.

Additional requirements when venting through 

a sidewall

1.  For sidewall venting, locate the humidifier as close as 

possible to the wall being used.

2.  Locate the vent terminal at least three feet above any 

forced air inlet located within ten feet; or at least four feet 

below, four feet horizontally from, or one foot above any 

door, window, or gravity air inlet into any building.

3.  A minimum horizontal clearance of four feet from electric 

meters, gas meters, regulator and relief equipment is 

required.

4.  For sidewall vent terminations, the humidifier must be 

installed with the certified vent terminal that can be 

purchased from Condair.

a.  Nortec GS 100 3”  P/N 1502321
b.  Nortec GS 200 4” P/N 1502322
c.  Nortec GS 300/400 5” P/N 1507320
d.  Nortec GS 500/600 6”  P/N 1507321

5.  Locate the vent terminal at least 7 feet or 2.1 m above 

grade from public walkways, adjacent buildings, operable 

windows and building openings, consistent with the 

National Fuel Gas Code ANSI Z223.1 and/or CSA B149.1 

installation codes.

6.  Locate the bottom of the vent terminal at least twelve 

inches above grade or ground, or normally expected snow 

accumulation level. The snow level may be higher on walls 

exposed to prevailing winds.

7.  Locate terminal at least 4 feet or 1.22 m from electric 

meter, gas meters, regulators, and relief equipment.

8.  Avoid areas where local experience indicates that 

condensate drip may cause problems such as above 

planters, patios, or over public walkways, or over an area 

where condensate or vapor could create a nuisance 

or hazard, or could be detrimental to the operation of 

regulators, relief valves, or other equipment. Refer to the 

vent manufacturer’s installation instructions.

9.  The vent terminal must be installed in the same 

atmospheric pressure zone as the combustion air inlet of 

the humidifier. If this is not possible (as in cases of positive 

or negative room pressures) the humidifier should be 

installed with the sealed combustion or direct vent option.

Содержание Nortec GS 100

Страница 1: ...Quick Start Installation Guide Venting NORTEC...

Страница 2: ...designed to burn solid fuel 8 This appliance may not be used in conjunction with a power venter or draft inducer 9 For any vent lengths over 20 feet long insulate the vent pipe to reduce the amount o...

Страница 3: ...Nortec GS 100 4 minimum diameter b Nortec GS 200 5 c Nortec GS 300 400 7 d Nortec GS 500 600 8 7 The termination at the humidifier is a male connection Standard venting hook ups require a female path...

Страница 4: ...inlet located within ten feet or at least four feet below four feet horizontally from or one foot above any door window or gravity air inlet into any building 3 A minimum horizontal clearance of four...

Страница 5: ...Venting Options Vertical with B Vent Vertical with B Vent and Sealed Combustion...

Страница 6: ...ical or Horizontal with BH Vent Vertical or Horizontal with BH Vent and Sealed Combustion Horizontal exhaust terminal must be certified and can be ordered from Condair If BH venting used orient vertic...

Страница 7: ...Options Direct Vent Vertical Co Venting Using B Type Terminate exhaust and intake horizontally only in same face of building Install Condair or by other certified terminals orient vertically 6 in fro...

Страница 8: ...r to the installation manual for your specific system accessories and components All electrical connections must be installed in accordance with local and national electrical code requirements by a li...

Отзывы: