Cleaning the Drain Valve and GFCI Plate
Scale from the spent cylinder may have fallen into the drain valve and may prevent proper
operation. Scale may also accumulate on the Ground Fault Circuit Interrupter (GFCI) plate. Clean
the drain valve and GFCI plate when substantial scale buildup is evident, especially if the scale
prevents the drain valve from sealing.
The drain valve must be removed and disassembled for it to be properly cleaned.
1
2
Figure 9 - Drain Valve Replacement
1. Ground connection
2. Ground fault circuit interrupter (GFCI) plate
Removing the drain valve:
(refer to
and
):
1. Remove the cylinder and plumbing cover.
Disconnect the spade connectors from the drain valve.
2. Remove the hoses connected to the drain valve. This will allow you to pull the drain valve
out easier.
3. Disengage the tab securing the left-side of the drain valve then lift the drain valve out of the
humidifier. The drain valve and GFCI plate can now be cleaned or replaced.
Condair RH
2594949_B_EN_2005_Condair-RH_OM
Maintenance | 19