Modbus
The Condair DA Desiccant Dryer supports Modbus RTU with RS 232 interfaces. Support for Modbus RS485 and
TCP/IP can be added with an optional communication card.
Table 8:
RS 232 Pin Interfaces
Pin #
RS 232 (Port 1)
1
Not connected
Signals are related to the controller’s 0V; the same 0 V is used by the power
supply.
The serial port is not isolated. If the controller is used with a non-isolated
external device,
avoid potential voltage that exceeds ± 10V
.
2
0V reference
3
TXD signal
4
RXD signal
5
0V reference
6
Not connected
Table 9:
Analog and Misc. Datapoints
RS232, ID: 35 Bitrate: 9600, Parity: None, Stop bits: 1
MBA
MBE
Format
Holding
Register
Coil
Status
Read/
Write
INFO
Text / Info
Var.
Analog inputs
70
R
Humidity sensor
% RH 0
100
##
76
R
0-10V dehumidification control
VDC
0.0
10.0
##.#
Analog setpoint
9
R/W
Humidity setpoint for humidity
sensor
% RH 50
-
##
Misc
2
R/W
1=On
Unit on/off
1/0
-
-
-
3
R
1=On
Urgent alarm
1/0
-
-
-
4
R
1=On
Non urgent alarm
1/0
-
-
-
13
R/W
1=On
Cooling time react. Air fan
1/0
-
-
-
15
R/W
1=Auto Unit automatic/manual mode
1/0
-
-
-
27
R/W
1=On
Continuous process air fan
1/0
-
-
-