Communication table
Data point
Object function
Description
Range
Type
…
Setpoint High Area [n]
Humidification level 3 "Humidifica-
tion High" of zone [n]
0 = inactive
1 = active
DPT 01
152
Setpoint High Area 20
Humidification level 3 "Humidifica-
tion High" of zone 20
0 = inactive
1 = active
DPT 01
153
Auto Modus Area 1
1)
Humidification level 4 "Auto
mode" of zone 1 (Control home
automation)
0 = inactive
1 = active
DPT 01
154
Auto Modus Area 2
1)
Humidification level 4 "Auto
mode" of zone 2 (Control home
automation)
0 = inactive
1 = active
DPT 01
…
Auto Modus Area [n]
1)
Humidification level 4 "Auto
mode" of zone [n] (Control home
automation)
0 = inactive
1 = active
DPT 01
172
Auto Modus Area 20
1)
Humidification level 4 "Auto
mode" of zone 20 (Control home
automation)
0 = inactive
1 = active
DPT 01
173
Setpoint Area 1
Humidification level of zone 1
0 = Off
1 = Humidification Low
2 = Humidification Mid
3 = Humidification High
4 = Auto mode
DPT 05
174
Setpoint Area 2
Humidification level of zone 2
0 = Off
1 = Humidification Low
2 = Humidification Mid
3 = Humidification High
4 = Auto mode
DPT 05
…
Setpoint Area [n]
Humidification level of zone [n]
0 = Off
1 = Humidification Low
2 = Humidification Mid
3 = Humidification High
4 = Auto mode
DPT 05
192
Setpoint Area 20
Humidification level of zone 20
0 = Off
1 = Humidification Low
2 = Humidification Mid
3 = Humidification High
4 = Auto mode
DPT 05
193
External Value Area 1
Setpoint setting by home automa-
tion in auto mode (humidification
level 4) of the zone 1
20 - 80%
DPT 09
194
External Value Area 2
Setpoint setting by home automa-
tion in auto mode (humidification
level 4) of the zone 2
20 - 80%
DPT 09
…
External Value Area [n]
Setpoint setting by home automa-
tion in auto mode (humidification
level 4) of the zone [n]
20 - 80%
DPT 09
212
External Value Area 20
Setpoint setting by home automa-
tion in auto mode (humidification
level 4) of the zone 20
20 - 80%
DPT 09
245
System Name Number
Serial number of the Condair MN
DPT 12
246
Number of Areas
Number of existing zones
1 - 20
DPT 05
247
Filter Change Necessary
Message "Filter Change Neces-
sary", the filter of the device is
exhausted and must be replaced
0 = OK
1 = Replacement required
DPT 01
248
Service Necessary
Collective message "Service"
The unit needs servicing, contact
customer service
0 = OK
1 = Service required
DPT 01