KNX & Amazon Echo (Alexa) interface
7. Set the following Modbus parameters via the SPA display or the integrated web interface under
"Engineering > SPA Control Board > Modbus Settings > Gateway":
Parameter
Value
Slave Address
1
Baud rate
19200
Parität
Even, 1 stop bit
Data Format
ABCD: big endian
For dual cabin application for medium size cabins, 2 SPA control boards must be connected to the
gateway. For the second SPA control board (Server ID 1), the Modbus slave address must be set to 2:
Parameter
Value
Slave Address
2
Baud rate
19200
Parity
Even, 1 stop bit
Data Format
ABCD: big endian
Setting via SPA display
Data Format
ABCD: big endian
Gateway
Baudrate
19200
Parity
even, 1 stop bit
Slave Address
1
Gateway