Concoa IntelliSwitch Maniflex 628 Series Скачать руководство пользователя страница 3

--

√ 

Always remove all empty cylinders from a manifold before connecting full cylinders.

√ 

Always test cylinders to be sure they are full before connecting to a manifold.

√ 

NOTE:  Use of Teflon

® 

lined pigtails for oxygen installations is not recommended unless they are equipped with a Distance Volume 

Piece (DVP). Components in the manifold system can create a dead end passage.  The combination of a dead end passage 

coupled with a rapid pressurization may lead to adiabatic compression of the contained oxygen and subsequent failure of the 

pigtail by ignition.

√ 

All gas distribution piping systems must meet appropriate industrial standards for the intended service, and must be thoroughly 

cleaned before using.

√ 

Keep all cylinders away from any source of high temperature (not over 120° F, 50° C) or possible fire hazards.  High-pressure gas 

contained in a closed cylinder becomes increasingly dangerous when exposed to high temperature because pressure increases 

and the strength of the cylinder decreases.

√ 

No smoking should be permitted near oxygen nitrous oxide, flammable gases and flammable mixtures and in area where cylinders 

are stored.

√ 

Where oxygen or nitrous oxide is used, the manifold and cylinders must be kept clean. No oil, grease, or combustible substances 

should come in contact with oxygen or nitrous oxide storage or handling equipment.  Such materials in contact with oxygen or 

nitrous oxide are readily ignitable and when ignited, will burn intensely.

√ 

Never lift gas cylinders with a magnetic lifting device.

√ 

Never use an open flame when leak testing.

√ 

Keep all cylinders away from any source of high temperature (not over 120° F, 50° C) or possible fire hazards.  High-pressure gas 

contained in a closed cylinder becomes increasingly dangerous when exposed to high temperature because pressure increases 

and the strength of the cylinder decreases.

√ 

No smoking should be permitted near oxygen nitrous oxide, flammable gases and flammable mixtures and in area where cylinders 

are stored.

√ 

Where oxygen or nitrous oxide is used, the manifold and cylinders must be kept clean. No oil, grease, or combustible substances 

should come in contact with oxygen or nitrous oxide storage or handling equipment.  Such materials in contact with oxygen or 

nitrous oxide are readily ignitable and when ignited, will burn intensely.

√ 

Never lift gas cylinders with a magnetic lifting device.

√ 

Never use an open flame when leak testing.

Comply with all safety rules and precautions of the following: 

1.  American National Standards Institute standard Z49.1 or Safety in Welding and Cutting, American Welding Society, 2501 NW 

Seventh Street, Miami, FL 33125.

2.  N.F.P.A. Standard 51, Oxygen-Fuel Gas Systems for Welding and Cutting, N.F.P.A., 470 Atlantic Avenue, Boston, MA 02210.

3.  N.F.P.A. Standard 51B, Cutting and Welding Processes, (see Address in #2)

4.  CONCOA Publication ADE 872, Safety Precautions in Welding and Cutting.

5.  Local ordinances.

6.  O.S.H.A.

7.  C.G.A. Pamphlet C-4, American National Standard Method of Marking Portable Compressed Gas Containers to Identify the Material 

Contained.*

8.  C.G.A. Pamphlet G-4, Oxygen-Information on the properties, manufacture, transportation, storage, handling, and use of oxygen.

9.  C.G.A. Pamphlet G-4.1, Equipment Cleaned for Oxygen Service.

10.   C.G.A. Pamphlet C-4.4, Industrial Practices for Gaseous Oxygen Transmission and Distribution Piping Systems.

11.  C.G.A. Pamphlet G-5, Hydrogen - Information on the properties, manufacture, transportation, storage, handling, and use of hydrogen.

12.  C.G.A. Pamphlet G-6, Carbon Dioxide - Information on the properties, manufacture, transportation, storage, handling, and use of 

carbon dioxide.

13.  C.G.A. Pamphlet G-6.1, Standard for Low Pressure Carbon Dioxide Systems at Consumer Sites.

14.  C.C.A. pamphlet P-1, safe handling of compressed gases in containers.

15.  C.G.A. Safety Bulletin SB-2, Oxygen Deficient Atmospheres.

*C.G.A. pamphlets can be obtained from the Compressed Gas Association, 1235 Jefferson Davis Highway, Arlington, VA 22202-3239, (703) 

979-0900. Publications: (703) 979-4341. Fax: (703) 979-0134.

REMOVAL

1. Disconnect AC Power from unit.

2. Shut off all pressure to unit and bleed off any pressure remaining in the lines and regulators.

3. Using a small flat blade screwdriver, remove the plug from the center of the Outlet Pressure adjustment knob.

4. Remove the nut holding the knob to the shaft.  DO NOT attempt to remove or adjust the nuts on the shaft underneath the knob.

5. Remove large nut and washer holding the bonnet to the cover.

6. Remove the four (4) screws holding the cover to the enclosure.

7. Carefully pull cover away from enclosure.

8. Disconnect all the cables connected to the Control Board.  It is recommended that each cable be marked identifying its location  

before removing.  Use Figure 1 as a guide.  The three (3) connectors coming from the transducers and the two connectors coming 

from the solenoids have locking tabs.  Squeeze the locking tab on each connector to remove it from the board.  Carefully remove 

the other connectors from the board.

9. Place the front panel in a secure location being careful not to scratch the front label.

10. The check valves are located on either side of the delivery regulator.  Using a hex wrench, remove the large brass check valve retainer.  

11. Carefully reach into the body and remove the pin and spring. If debris is found it should be removed.

Содержание IntelliSwitch Maniflex 628 Series

Страница 1: ...ION INSTRUCTIONS Before Installing or Operating Read and Comply with These Instructions Controls Corporation of America 1501 Harpers Road Virginia Beach VA 23454 To Order Call 1 800 225 0473 or 757 422 8330 Fax 757 422 3125 www concoa com June 2007 Certified ISO 9001 2000 ADI 6405 A ...

Страница 2: ...r specifications The user is responsible for selecting equipment compatible with the gas in use and conditions of pressure temperature flow etc Selection information can be found in CONCOA technical data sheets In addition CONCOA representatives are trained to aid in the selection process 3 Inspect the assembly upon receipt to be sure that there is no damage or contamination Pay particular attenti...

Страница 3: ...d Cutting American Welding Society 2501 NW Seventh Street Miami FL 33125 2 N F P A Standard 51 Oxygen Fuel Gas Systems for Welding and Cutting N F P A 470 Atlantic Avenue Boston MA 02210 3 N F P A Standard 51B Cutting and Welding Processes see Address in 2 4 CONCOA Publication ADE 872 Safety Precautions in Welding and Cutting 5 Local ordinances 6 O S H A 7 C G A Pamphlet C 4 American National Stan...

Страница 4: ...g the front panel to the bottom of the enclosure 5 Apply AC Power to the unit 6 Apply pressure to the unit 7 Test for leaks at the repair If using the wet method for leak checking make sure the control board does not get wet 8 If no leaks turn pressure off and remove AC power again 9 Place the front panel back into place being careful not to pinch any wires 10 Attach the four 4 screws and washers ...

Страница 5: ...er You will be asked to provide 1 Model Number 2 Gas Service 3 Inlet pressure and type of gas supply 4 Outlet pressure 5 Approximate gas usage When shipping product back to CONCOA for repair the following steps should be followed 1 Package the product sufficiently to prevent damage If possible return product in its original packing 2 Include RMA number on the outside of the carton 3 Ship prepaid 4...

Страница 6: ... THIS PAGE INTENTIONALLY LEFT BLANK ...

Страница 7: ... other than Controls Corporation of America or if the equipment has been subject to abuse misuse negligence or accident Controls Corporation of America s sole and exclusive obligation and Buyer s sole and exclusive remedy under the above warranties is limited to repairing or replacing free of charge at Controls Corporation of America s option the equipment or part which is reported to its Authoriz...

Страница 8: ...Controls Corporation of America 1501 Harpers Road Virginia Beach VA 23454 To Order Call 1 800 225 0473 or 757 422 8330 Fax 757 422 3125 www concoa com June 2007 Certified ISO 9001 2000 ADI 6405 A ...

Отзывы: