All output monitors on the Thermolator can be enabled or dis-
abled permanently through the OM Enable/Disable Menu in
Test Mode.
You need to use this feature if you have replaced the mother-
board, or if dip switches 7 and 8 have been changed erro-
neously. This will enable any required output monitors that
were disabled and give fuse failures.
Press any key to display the first test menus.
Select the OM Enable/Disable menu.
Press and hold the Setpoint key for 3 seconds to index
to each test menu until the controller indicates “oS1” in
the actual display and the status of the selected output in
the Select display.
Press the Setpoint
▲
▲
or
▼
▼
key to change the
status.
Each press of the key changes the output status
from ON to OFF or OFF to ON.
Press the Setpoint to select the next output.
Repeat Step 4 to change the status of the output, or press
any key to continue indexing through the outputs.
Save changes and exit the output menu.
Press and hold the Select key for 3 seconds to save the
changes and exit.
D
ISABLING OR
E
NABLING
O
UTPUT
M
ONITORS
UGH015/0100
Thermolator TW-1 and TW-2
M
AINTENANCE
5-9
1
2
3
4
5
6
O
UTPUT
M
ONITOR
S
ELECTION
G
UIDE
MODEL TYPE
DI
CC
IC (TCC)
OM1 Pump
ON
ON
ON
OM2 Heat
ON
ON
ON
OM3 Cool
ON
ON
ON
OM4 Vent
OFF
ON
OFF
OM5 Purge (TW-2 option only)
ON
ON
OFF
Содержание Thermolater vacuTrac
Страница 9: ...Figure 1...
Страница 12: ......
Страница 15: ......
Страница 16: ......
Страница 50: ......
Страница 62: ......
Страница 100: ......
Страница 106: ......
Страница 117: ...UGH015 0100 TW 1 230 460V WIRING DIAGRAM PD 5...
Страница 119: ...UGH015 0100 TW 2 230 460V WIRING DIAGRAM PD 7 2...