26
dXX
Function
Parameter
Values
Description
Default
Values
d05
Cooling mode control
method
1
SPAN ± 0.5°C (± 1°F)
2
2
SPAN ± 1°C (± 1.5°F)
d06
Type of thermoelectric
actuator
0
NO - normally open
1
1
NC - normally closed
d07
Valve Protection
Valve protection function is intended to protect thermostatic valves against getting stuck
or jamming (e.g. in summer time when heating system is disabled). If thermostat doesn’t
send a signal for heating for a period of 7 days, then heating is turned on for a very short
period of time just to move the actuators.
1
0
OFF
1
ON
d08
Frost protection
temperature
5-17°C
In Frost protection mode the thermostat is displaying actual room
temperature and maintain „frost protection” setpoint temperature specified
in thermostat settings. When thermostat works in Frost protection
mode then you have no possibilities to change temperature setpoint.
5.0°C
d09
Clock format
0
12 hours
1
1
24 hours
d10
Time zone (reserved for
internet wireless)
from -13 to
+13 hours
It gives you the possibility to fit the thermostat time zone to yours
(every 1 hour step).
0
d11
Daylight Saving Time
(DST)
0
Off
1
1
On
d12
Heating temperature
limit
5°C - 35°C
The maximum heating temperature that can be set
by the user
35°C
d13
Cooling temperature
limit
5°C - 40°C
The minimum cooling temperature that can
be set by the user
5°C
d14
Maximum floor temperature
(this function is active
in heating mode when
d04 = 1)
6°C - 45°C
In order to protect the floor from overheating, heating will be turned OFF,
when the maximum temp. of the floor sensor will be reached.
27°C
d15
Minimum floor temperature
(this function is active
in heating mode when
d04 = 1)
6°C - 45°C
In order to protect the floor, heating will be turned ON, when the
minimum temp. of the floor sensor will be reached
10°C
d16
Lower floor temperature
limit for cooling
(this function is active
when d04 = 1)
6°C - 45°C
In order to protect the floor, cooling will be turned OFF, when
the minimum temperature will be reached
6°C
d17
Choice of the default
program
1-5
Selection 1 of the 5 default programs
1
d18
Operating mode
HEATING / COOLING
0
Heating system
0
1
Cooling system