Refer to the unit rating  plate for wire sizing information and  maximum fuse or "HACR Type" 

circuit breaker size.  Each outdoor unit is marked with a 

Circuit 

This means 

that the field wiring used  must 

be 

sized  to carry that amount of current.  Depending on the 

installed 

of electric heat, there may 

be 

two field power circuits required.  If this is the 

case, the unit serial plate will so indicate. 

All 

are suitable only for connection with 

copper wire.  Each unit and/or wiring diagram wi 

be 

marked "Use Copper Conductors 

y".  These 

instructions MUST 

BE 

adhered 

to. 

Refer to the National  Electrical Code (NEC)  for complete 

current carrying capacity data on the various insulation grades of wiring material. 

All 

wiring 

must conform to NEC and all local codes. 

The electrical data lists fuse and wire sizes 

copper) for all models, including the most 

used heater sizes.  Also shown are the number of field power circuits required for the 

various models with heaters. 

The unit rating plate  ists a "Maximum Time Delay Relay Fuse" or "HACR Type" circuit breaker that 

is to be used with the equipment.  The correct size must 

be 

used for proper circuit protection 

and also to assure that there will 

be 

no 

nuisance tripping due 

to 

the momentary high starting 

current of the compressor motor. 

SERVICE HINTS 

1. 

Caution homeowner to maintain clean air filters at all times.  Also, not to needlessly 
close off supply and return air registers.  This reduces air flow through the system, 

which shortens 

service life as well as increasing operating costs. 

2. 

Switching to heating cycle at 

or higher outside temperature may cause a nuisance 

trip of the 

reset high pressure switch.  Turn thermostat off, then on the reset 

the high pressure switch. 

3. 

The heat pomp wall thermostats perform multiple functions. 

Be 

sure that all function 

switches are correctly set for the desired operating mode before trying to diagnose any 
reported service problems. 

4. 

Check all power fuses or circuit breakers to be sure they are the correct rating. 

5. 

Periodic  cleaning  of  the  outdoor  coil  to  permit  full  and  unrestricted  airflow 

circulation is essential. 

Содержание CELAC

Страница 1: ... OPERATION MAINTENANCE AND PARTS MANUAL CELLU KOOL SERIES MODEL TYPE SIZE CELHP HEAT PUMP 1 TO 5 TON CELAC AIR CONDITIONER 1 TO 5 TON COMPU AIRE INC 8167 BYRON RD WHITTIER CA 90606 PH 562 945 8971 FAX 562 696 0724 ...

Страница 2: ... i r Conditioning and Equipment Selection ANSI NFPA 90A ANSI NFPA 908 ACCA Manual 3 ACCA Manual D F O R M O R E INFORMATION CONTACT THESE PUBLISHERS ACCA AIR CONDITIONING CONTRACTORS O F AMERICA 1513 16th Street N W Washington DC 20036 Telephone 202 483 9370 Fax 202 234 4721 ANSI AMERICAN NATIONAL STANDARDS INSTLTUTE 1 1 West Street 13th Floor New York N Y 10036 Telephone 212 642 4900 Fax 212 302 ...

Страница 3: ...L EVAPORATOR COIL EVAPORATOR BLOWER I HIGH EFFICIENCY MOTOR H 7 HIGH COMPRESSOR AGE CONTROL PANEL CONDENSER COIL MODEL DESIGNATIOX 3 3 4 HASE I SINGLE PHASE 3 THREE PHASE YSTEM CAPACITY 2 2TON 3 3TON 4 4 TON YSTEM TYPE AC AIR CONDITIONER HP HEAT PUMP ERTICAL WALL HUNG UNITS ...

Страница 4: ......

Страница 5: ...SS P m L FILTER AND BLOWER MOTOR FREE CONDENSER AIR INLET Ur C0N DESATE DRAIN 1 2 M0UNTING HOLE FREE COOLrNG AIR INLET CONDENSER AIR INLET REAR VIEW ACCESS CONDENSING FRONT VIEW MoToR dr FAN 6187 BTmN R a m vlmlmR a BOW6 r ...

Страница 6: ...FIGURE 7 COOLING COIL DAMPER BLADE OUTSIDE AIR COND AIR CONDENSER 1 I EXHAUST AIR ...

Страница 7: ...re critical of proper operating charge and an adequate duct system than a straight air conditioning unit All duct work supply and return must be properly sized for the design air flow requirement of the equipment Air Conditioning Contractors of America ACCA is an excellent guide to proper sizing A11 duct work or portions thereof not in the conditioned space should be properly insulated in order to...

Страница 8: ...ngs in the unit base for the drain hose to pass through In the event the drain hose is connected to a drain systea of some type it must be an open or vented type system to assure proper drainage INSTALLATION INSTRUCTIONS WALL MOUNTING INFORMATION 1 Two holes for the supply and return air openings must be cut through the wall as shown in Figure 2 2 O n wood frame walls the wall construction must be...

Страница 9: ... to observe required clearance if combustible wall On side by side installations maintain a minimum of 20 inches clearance on right side to allow access to control panel and heat strips and allow proper airflow to the outdoor coil Additional clearance nay be required to meet local or national codes TOP OUTLET ONLY R e m e axframe angles from the back of the unit Coat angles with 2 118 beads of sil...

Страница 10: ... BEAD OF SILICONE CAULKING BE PLACED BEHIND TEE SIDE W O W I N G FLANGES AND UNDER T E TO FLASHING F FWI AIR SEK WE I1 1s R E U I I C M B nu1 A BW1a SlllCDH W W G BE mmtlmME S l E m 1 H 6 s 1 f f A l I l I E f f IKSIMLAIIM ...

Страница 11: ...aces WARNING A nininus of 114 clearance must be namtained between the supply air duct and conbustible naterlals This is required for the first 3 feet of ducting 1 I IIt is important to insure that the lt4 mininun spacing is maintained at all pints I Failure to do this could result in overheating the mnbuntible material and nay result in a fire I ...

Страница 12: ...FIGURE 2B ...

Страница 13: ...s with heaters The unit rating plate 1ists a Maximum Time Delay Relay Fuse or HACR Type circuit breaker that is to be used with the equipment The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor SERVICE HINTS 1 Caution homeowner to maintain clean air filters at all t...

Страница 14: ...ERVICE PORTS High and low pressure service ports are installed on all units so that the systen operating pressures can be observed Pressure curves can be found later in the nanual covering all nodels on both cooling and heatlng cycles It is imperative to match the correct pressure curve to the unit by nodel number DEFROST CYCLE The defrost cycle is controlled by temperatureand time on the solidsta...

Страница 15: ...oot indoor unit and correct problem 3 Turn thermostat blower switch to auto position Indoor blower should stop 4 Set system switch to heat or cool Adjust thermostat to call for heat or cool The indoor blower compressor and outdoor fan should start NOTE If there was no power to 24 volt transformer the compressor and outdoor fan motor will not start for 5 minutes This is because of the compressor sh...

Страница 16: ...sions below be checked and blade adjusted in or out on the motor shaft accordingly REMOVAL OF THE FAN SHROUD 1 Diconned all power to unit 2 Reme the screws holding both grills one on each side of unit and remove grills 3 Reme screws holding fan shroud t o condenser and batton 9 screws I Unwire condenser fan motor 5 Slide complete motor fan blade and shroud asseably out the left side of the unit 6 ...

Отзывы: