background image

 
 

 

 

34

 

15

 

START-UP AND TEST PROCEDURE 

15.1

 

Check that ALL WIRING IS CORRECT 

To perform this test the unit must be turn OFF. Check that properly sized fuses are installed in the 
disconnect switch.  Correct fuse size and minimum circuit ampacity are listed on the unit 
nameplate.  Now, check the wiring connections in the Main Control Panel to see if they are tight.  
It is best that this be checked prior to operating the machine. After checking, close the Main 
Control Panel cover and proceed as follows: 

Microprocessor Control Panel – With the system switch in the “OFF” position, apply power to the 
unit.  The “Power ON” light should illuminate. 

15.2

 

Check for Correct Phasing 

The equipment should now be checked for correct phasing required to make the blower motor 
turn in the correct directions.  For this test it is necessary to open the right side doors of the unit 
to observe the blower and blower motor.  Now, momentarily switch the system switch to the 
“ON” position and then back to “OFF”.  The blower motor with have started and it is therefore 
possible to determine rotation.  On Compu-Aire units, the blower should be rotating in a 
CLOCKWISE direction in downflow units and COUNTERCLOCKWISE direction in upflow units, 
looking in the right side of the unit.  Heaters and humidifiers are not affected by phasing. 

15.3

 

Fan Speed Adjustment  

Adjustment of the air flow maybe desired.  The air flow can be readily adjusted with the variable 
pitch pulley provided on the blower motors.  After the unit has been started and the air flow 
properly adjusted, check the blower motor current to ensure is increased, the blower motor 
current should be checked.  If a field adjustment is made, the motor should run for at least one 
hour at maximum design room temperature to see if motor trips on internal overload.  For 
proper motors amps refer to the name plate.   

15.4

 

 No air flow & Clogged filter adjustment 

The "No Air Flow" light and alarm should be checked prior to the completion of the installation. 
Although  the  control  adjusted  at  the  factory,  varying  local  conditions  make  it  impossible  to 
provide accurate pressure adjustments. 

To check  the  filter pressure  switch, let  the  unit operate on cooling for about 30 minutes. This 
will  allow  the  evaporator  coil  surface  to  become  wet.    The  air  pressure  differential  switch  is 
provided with adjustable knob. Set the knob to desire pressure drop for dirty filter and verify the 
Dirty Filter alarm.  With the unit cooling and filters in place, block off approximately 75% of the 
air  intake.    If  the  sensing  device  is  correctly  adjusted,  the      "Clogged  Filter"  alarm  should 
energize;  the  sensing  device  should  have  just  turned  on  the  alarm  at  the  75%  blocked  inlet 
condition. An Air Flow Sail switch is also provided at the discharge side of the blower and will 
activate the No Air Flow malfunction light and alarm. 

Содержание CAG-30 Series

Страница 1: ...1 SYSTEM 2100 GLYCOL COOLED CAG 30 ENERGY MISER INSTALLATION AND OPERATION MANUAL 8167 Byron Road Whittier CA 90606 Phone 562 945 8971 Fax 562 696 0724 www compu aire com...

Страница 2: ...Units 15 6 1 2 Upflow Units 15 6 2 Connections 16 6 2 1 Structural Support 16 6 2 2 Electrical Support 16 6 2 3 Condensate Drain Connection 16 6 2 4 Water Connection 17 6 2 5 Electrical Connection 19...

Страница 3: ...NG CONNECTION LAYOUT 33 14 1 WATER GLYCOL LINE CONNECTION 33 15 START UP AND TEST PROCEDURE 34 15 1 Check that ALL WIRING IS CORRECT 34 15 2 Check for Correct Phasing 34 15 3 Fan Speed Adjustment 34 1...

Страница 4: ...ample Unit Shown 29 Figure 10 Condenser and Reheat elements access 30 Figure 11 Unit Side Layout 30 Figure 12 Rear Open Floor Stand 31 Figure 13 Terminal Block with System Cut Out 32 Figure 14 Piping...

Страница 5: ...ing installation or servicing of a System 2100 series Below is general safety information as well as descriptions of safety and accident prevention symbols that will be utilized throughout this docume...

Страница 6: ...ntially hazardous situation which if not avoided could result in death or serious injury Indicates a potentially hazardous situation which if not avoided may result in minor or moderate injury Caution...

Страница 7: ...n specially trained and qualified in the installation or servicing of HVAC equipment Improper installation may result in unaccountable loss or damage EQUIPMENT TRANSPORTATION PROPER BRACING HIGH SPEED...

Страница 8: ...freezing temperatures and contact damage EQUIPMENT TRANSPORTATION Prior to transporting unit to final installation location ensure that there are no risks of overhead interference Relevant measuremen...

Страница 9: ...ATURES AND OR CORROSION Refrigerant leaking from the unit coil or piping due to freezing and or corrosion can cause serious equipment and building damage Use of proper antifreeze and inhibitors can pr...

Страница 10: ...Time Monday through Friday except holidays or you may send a facsimile message at 562 696 0724 anytime Finally you may write us at Compu Aire 8167 Byron Road Whittier CA 90606 Please do not return sys...

Страница 11: ...l codes and safety requirements to install and service this unit WARNING Installation and service of this equipment should be done by qualified personnel who have been specially trained and qualified...

Страница 12: ...water runs freely through the drain system Improper installation application and service practices can result in water leakage from the unit Water leakage can cause severe property damage and loss of...

Страница 13: ...ted as field installed shall be packaged inside of the unit and must be removed and installed prior to startup of the equipment Optional articles such as jack stand parts condensate pump and remote co...

Страница 14: ...d floor or on adjustable jackstands The unit should not be placed near any corner of the room For best air distribution the unit should be place in mid point against the unit should be place in mid po...

Страница 15: ...tion as well as the electrical power input locations are matching with unit location requirement Proper electrical supply power is an absolute necessity as the unit is designed specifically for the re...

Страница 16: ...nit bottom or the top panel on the unit Be sure unit is properly grounded A fused disconnect must also be provided for the air cooled condenser condensing unit for air cooled units and dry fluid coole...

Страница 17: ...close circuit dry fluid cooler is to be used A pump package for field install by other is generally included in the system with separate cabinet unit Provide a shut off valve in supply and return lin...

Страница 18: ...18 Figure 4 Typical Unit Field Piping Connection...

Страница 19: ...ox Supply voltage at the unit must be within 10 of the voltage indicated on the nameplate for a dual voltage rating supply voltage must be within 5 from the lower nameplate rating and within 10 from t...

Страница 20: ...ed if the system contains more than 20 lbs 9 kg of refrigerant add one fluid ounce for every additional 5 pounds 15ml kg of refrigerant over this amount 7 1 1 Evacuation Procedures CAUTION PULL ALL FU...

Страница 21: ...on for 2 hours and re check the gauge readings Purge with Freon and re pull the vacuum of 250 microns 9 842 in hg or less After the completion of this step fill the system with Freon vapor until pres...

Страница 22: ...tentionally blowing the charge is illegal The procedure for saving the refrigerant charge is as follows 1 Open disconnect switch 2 Pull fuses on system not to be opened 3 Install manifold on the recei...

Страница 23: ...23 8 GENERAL WIRING DIAGRAM WATER GLYCOL COOLED 30 35 TON SYSTEM 2200 CAG EM WITH NORTEC HUMIDIFER ELECTRIC REHEAT 682 447 420...

Страница 24: ...THE UNIT 9 1 System Testing The performance of all control circuits can be tested by actuating each of the main functions This is done by temporarily changing the set points 9 1 1 Cooling To test the...

Страница 25: ...advanced OEM steam humidifier and provides steady and reliable humidification using the same proven cylinder technology as Nortec s commercial NHTC Depending on the unit configuration the steam humid...

Страница 26: ...used in Compu Kool III unit is the electrical heating elements The number of the stages and elements depend on heating required for dehumification Figure 6 Reheat Elements 9 4 Condensate Pump optional...

Страница 27: ...d to check the manufacturer s literature for more detail of the dry fluid cooler prior the unit installation PUMPS FOR CKG MODELS These are shipped from Compu Aire along with the air conditioners unit...

Страница 28: ...CREEN DISPLAY LOCKING DISCONNECT SWITCH EC FAN MOTOR ACCESS DOOR COIL BLOWER MOTOR ACCESS DOOR CONTROL PANEL ACCESS DOOR FRONT ACCESS 132 50 SUPPLY AIR DUCT FLANGE 36 MIN CLEARANCE 38 MIN CLEARANCE 38...

Страница 29: ...TIFICATION ACCESS 11 1 FRONT LAYOUT CONTROL BOX Figure 9 Sample Unit Shown Actual unit may be different NUMBER NAME 1 DISCONNECT SWITCH 2 CONTACTORS 3 MOTOR PROTECTORS 4 MICROPROCESSOR CONTROLLER 5 TR...

Страница 30: ...Reheat elements access 11 3 SIDE LAYOUT Figure 11 Unit Side Layout 1 HUMIDIFIER 2 COMPRESSOR 3 HOT GAS BYPASS VALVE SOLENOIDS ETC 4 PIPING CONNECTION 1 2 3 4 REHEAT ELEMENTS PRESSURE REGULATING VALVE...

Страница 31: ...31 11 4 STANDARD FLOOR STAND Figure 12 Rear Open Floor Stand Doc No FM 7 3 3 03 REV A SUBJECT TO CHANGE WITHOUT INCURRING OBLIGATION OF Specialized Environmental Air Conditioning Systems...

Страница 32: ...ematic shut down by the controller programming Remote ON OFF relays can be disabled from controller programming and unit may not shut down in case of emergency 13 REMOTE ALARMS One Alarm Relay with a...

Страница 33: ...ting pressure not to exceed 125 PSIG Optional high pressure rated valve is available from the factory Unless specified water glycol piping connection s are located on the left bottom corner of the sta...

Страница 34: ...Speed Adjustment Adjustment of the air flow maybe desired The air flow can be readily adjusted with the variable pitch pulley provided on the blower motors After the unit has been started and the air...

Страница 35: ...alarm is activated the filter pressure switch If the filters are dirty they must be changed for efficient operation of your system To check the alarm indicator cover approximately 75 of the return ai...

Страница 36: ...the system 6 Ensure that the condenser surface if applicable is cleaned and free of dirt and debris 7 Check the operation of the control system Make certain that all of the safety controls are operat...

Страница 37: ...37 17 REFERENCE DOCUMENTS...

Страница 38: ...38...

Страница 39: ...utton on MCP then press On button If the system does not start or if the display still shows erroneous information replace the MCP Complaint Problem Symptom Action 2 Nothing is visible on the display...

Страница 40: ...tests are okay swap connections between pins 14 and 16 and observe whether dis play tracks each okay If it does replace the sensor If it doesn t replace the MCP Complaint Problem Symptom Action 4 Sen...

Страница 41: ...ot opening because of loose or broken wiring Display shows chilled water cooling is on or economy cooling is on but the valve is closed Test for 24VAC at valve motor Check continuity between pins 3 an...

Страница 42: ...MCP terminal connector Test at pin 30 only if stage two is off Test at both 30 and 33 if stage two is on If no voltage at pin 27 or if voltage at each check back to system terminal block and heater co...

Страница 43: ...fer to the section in this guide DIP Switch Settings and make sure the switches are set correctly 10 System occasionally forgets control settings Battery is dead If the system is turned off for a few...

Страница 44: ...flow fire stat water on floor or smoke detector alarm is activated The display shows one or more of these alarms and the Alarm LED is on The system is automatic ally shut down if any of these conditio...

Страница 45: ...116 252 Electrical Parts Humifidifier Capacity lbs 30 0 262 130 331 Contactor 274 040 323 274 030 336 Aux Switch 274 100 034 Fuse 15 A 271 160 515 20 A 271 160 520 25 A 271 160 525 40 A 271 260 440 Tr...

Страница 46: ...302 Touch Screen Display Temp Hum Sensor 254 744 302 Connector Kit 254 743 302 NTC Sensor 254 445 002 Communication Card pCOnet BACnet OVER MS TP 254 549 004 pCOWEB ETHERNET INTERFACE 254 549 003 LON...

Страница 47: ...cing filters humidifier cylinder infra red lamps float valve assemblies belts cleaning lubrication calibration and adjusting are NOT INCLUDED in this warranty Replacement or repair parts shall be ship...

Страница 48: ...562 696 0724 Fax While every precaution has been taken to ensure the accuracy and completeness of this literature Compu Aire assumes no responsibility and disclaims all liability for damages resulting...

Отзывы: