8/10
power class. The necessary information
can be found in chapter 4.1: Conditions for
electrical connection.
If no foundation plate is integrated in the foun
-
dation, proceed as follows:
1.
Pull the supply cables through the legs of
the column.
2. Place the box on the foundation and align
the column.
3.
Use the column base as a drilling temp-
late and fasten the box with four suitable
dowels, washers and screws.
4.
Connect the supply cable according to the
power class. The necessary information
can be found in chapter 4.1: Conditions for
electrical connection.
5 Safety tests
After the electrical connection of the charging
station, carry out the necessary safety tests.
•
Before commissioning the charging station,
check the effectiveness of the protective
measures of the complete system accor-
ding to the applicable national and local
regulations.
• The measuring instruments used must
comply with national regulations.
• Among other things, the Gossen Metra-
watt PROFiTEST MTECH+ protective mea
-
sures tester with manufacturer no. M520R
is required for testing the charging station.
Alternatively, use the Metrel MI 3152
EurotestXC ST. If none of the test devices
is available to you, the missing tests must
be performed by a Compleo specialist
partner.
•
Enter the result of the test in a test report.
A test report can be obtained from Com-
pleo Connect GmbH upon request.
• Give the test report to the customer, who
will send it to the manufacturer.
6 Technical data
Type
Payment terminal
Charging capacity
1 A, 230 V, 1-phase
Dimensions
(H x B x T)
300 x 300 x 165 mm
Weight
approx. 7,5 kg
Control fuse
1-pole, B6
Housing lockable
optional
Interfaces
Ethernet RJ45, RS485
Logs
Modbus TCP/RTU
Storage temperature
range
-30 to +70°C
Operating temperature
range
-25 to +55°C
Relative humidity
30 to 95 % (non-conden-
sing)
Protection class
1
Protection degree
IP54
Mechanical impact pro-
tection
IK 8
Rated voltag Un
230 V / 400 V AC
Rated operational voltage
Ue
220/380 - 240/415 V 3N
Rated insulation voltage Ui
500 V
Rated impulse withstand
voltage Uimp
4 kV
Overvoltage category
Kategorie III
Rated current of a circuit
Inc
Fused 6 A on the control
side
Rated peak withstand
current Ipk
<6 kA
Rated short-time with
-
stand current Icw
6 A
Rated conditional short-
circuit current Icc
6 A
Rated frequency fn
50/60 Hz
Pollution degree
3
System according to type
of earth connection
TN or TT
Installation site
Indoor and outdoor ins-
tallation
EMC classification
Class B
Содержание X-pay
Страница 1: ...Installation manual Compleo X pay 215041 b 02 2022...
Страница 2: ...2 10...
Страница 9: ......