P = setting parameters

DIAMIX PR / COMPAMIX PR

14

COMPARATO NELLO SRL

            

Cl1          

            
            

 

            

Cl2          

            
            

 

            

Cl3          

            
            

 

            

Cl4          

            
            

 

            

Cl5          

            
            

 

Where XX (%) indicates the maximum relative humidity for the tracking cooling.                                                                                                                                                    
Press “A” or “B” to set the value.                                                                                                                                                                                                                              
Press “C” to save the value and exit the sub-menu.                                                                                                                                                                                                  
Adjustment range: 20% to 90% (default 55%).  
Where XX (°C) shows the reference temperature for the integrator control.                                                                                                                                                             
Press “A” or “B” to set the value.                                                                                                                                                                                                                              
Press “C” to save the value and exit the sub-menu.                                                                                                                                                                                                  
Adjustment range: 20°C - 30°C (default 24°C). 
Where C (°C) indicates the temperature for calculating the Tset.                                                                                                                                                                               
Press “A” or “B” to set the value.                                                                                                                                                                                                                              
Press “C” to save the value and exit the sub-menu.                                                                                                                                                                                                  
Adjustment range: -3°C - +3°C (default 0°C). 
Where XX (%) indicates the hysteresis on the relative humidity control.                                                                                                                                                                  
Press “A” or “B” to set the value.                                                                                                                                                                                                                              
Press “C” to save the value and exit the sub-menu.                                                                                                                                                                                                  
Adjustment range: 2% to 15% (default 5%).  
Where XX (°C) indicates 

Δ

t activation of integrator command.                                                                                                                                                                                 

Press “A” or “B” to set the value.                                                                                                                                                                                                                              
Press “C” to save the value and exit the sub-menu.                                                                                                                                                                                                  
Adjustment range: 0°C - 15°C (default 5°C).                                                                                                                                                                                                             

MAIN 

MENU

SUB-MENU

FUNCTION

            

XX          

            
            

 

            

XX          

            
            

 

            

X            

            

 

            

XX          

            

 

            

XX          

            

 

            

P1           

            
            

 

            
            

P2           

            
            

 

            
            

P3           

            
            

 

            
            

P4           

            

 

            

ID           

            

 

Where X.X (sec) indicates the outlet temperature sampling range.                                                                                                                                                                           
Press “A” or “B” to set the value.                                                                                                                                                                                                                              
Press “C” to save the value and exit the sub-menu.                                                                                                                                                                                                  
The adjustment range is from 1.0 sec. to 10.0 sec. (default, 3.0 sec).  
Where XX (sec) indicates the delay time of the adjustment function from the room thermostat) inlet.                                                                                                                     
During this time, the relay output is activated (closure of the M3 contact).                                                                                                                                                               
Press “A” or “B” to set the value.                                                                                                                                                                                                                              
Press “C” to save the value and exit the sub-menu.                                                                                                                                                                                                  
The adjustment range is from 0 sec. to 100 sec. (default, 30 sec).  
Where XX (°C) indicates the maximum temperature above which the valve is forced on the radiant system return,                                                                                                
excluding any other active function.                                                                                                                                                                                                                          
Press “A” or “B” to set the value.                                                                                                                                                                                                                              
Press “C” to save the value and exit the sub-menu.                                                                                                                                                                                                  
Adjustment range: 53°C - 60°C (default 55°C). 
Where XX (°C) indicates the minimum temperature below which the valve is forced on the radiant system return,                                                                                                 
excluding any other active function.                                                                                                                                                                                                                          
Press “A” or “B” to set the value.                                                                                                                                                                                                                              
Press “C” to save the value and exit the sub-menu.                                                                                                                                                                                                  
Adjustment range: 5°C - 13°C (default 10°C). 
Where XXX is the Modbus address of the device – REMOTE MANAGEMENT.                                                                                                                                                           
Press “A” or “B” to set the value.                                                                                                                                                                                                                              
Press “C” to save the value and exit the sub-menu.                                                                                                                                                                                                  
Adjustment range from 0.1 to 255 sec (default 5).                                                                                                                                                                                                    

MAIN 

MENU

SUB-MENU

FUNCTION

            

X.X          

            
            

 

            
            

XXX         

            
            

 

            
            

XX          

            

 

            
            

XX          

            

 

            

XXX         

            

 

To access the menu, when the display shows the "OFF" indication, press the "A" or "B" buttons. The display will show the "P1" indication. Scroll the main menu with the “A” and “B” buttons. Press the "C" button to 
enter the sub menu. 

Содержание Compamix PR

Страница 1: ...VER 0 20 ...

Страница 2: ...________ Features of the actuator _______________________________________________________________________________________________ Features of the ball valve __________________________________________________________________________ Installation __________________________________________________________________________ Electrical connections _________________________________________________________...

Страница 3: ...g cooling adjustment The delivery temperature Tset_point for cooling is automatically calculated by the software as a function of the dew point temperature The dew point temperature is calculated by means of the relative humidity and ambient temperature sensor optional cod RFTRUEE10 T_setpoint Trugiada CI3 where Trujade Dew temperature calculated from relative humidity and ambient temperature CI3 ...

Страница 4: ...617N 4 ROD BRASS CW617N 5 BALL SEAL P T F E 6 SEAL P T F E 7 O RING FKM 1 BODY BRASS CW617N 2 COUPLING BRASS CW617N 3 BALL CHROMED BRASS CW617N PTL 4 ROD BRASS CW614N 5 BALL SEAL P T F E 6 SEAL P T F E 7 O RING EPDM with union with union values referring to the most disadvantaged way L values referring to the most disadvantaged way L Code DN Δp max bar PN Connections Mixing KvS m3 h 20 G 3 4 16 16...

Страница 5: ...Mounting the actuator facing downwards is not allowed Once installed the actuator connection should not be at the bottom of the valve SUBMERSIBLE OUTLET TEMPERATURE SEENSOR As an alternative to the cuff sensor the immersion sensor is available as an option It must be placed on the temperature controlled outlet M or AB using a G3 8 female well not included The sensor is fitted with a connector for ...

Страница 6: ...RETURN RADIANT SYSTEM RETURN RADIANT FLOW FROM PRIMARY SYSTEM VALVE POSITION COMPLETELY HOT DIAMIX PR COMPAMIX PR 6 COMPARA TO NELLO SRL DIAMIX PR COMPAMIX PR LINE MIXED DIAMIX PR ISO 5211 CONNECTION DIAMIX PR ISO 5211 CONNECTION FLOW FROM PRIMARY SYSTEM FLOW FROM SYSTEM PRIMARY SYSTEM RETURN RADIANT SYSTEM RETURN RADIANT OUTLET MIXED OUTLET MIXED VALVE POSITION COMPLETELY HOT A AB B ...

Страница 7: ...VDC POWER SUPPLY CABLE 5 x 0 5mm 2 SIGNAL CABLE 15 x 0 5mm 2 DIGITAL OUTLETS DIGITAL INLETS OUTDOOR TEMPERATURE PROBE ANALOG INPUT RELATIVE HUMIDITY AMBIENT TEMPERATURE PROBE MIXED TEMPERATURE PROBE RS485 Modbus RTU 230V 50 60 Hz 24V 50 60 Hz PUMP CONTROL Max 250V 1A D D PHASE NEUTRAL TEMPERATURE AND RELATIVE HUMIDITY SENSOR RFTRUEE10 INTEGRATION 24V DC CONTROL RELAY SUMMER WINTER CONTROL RELAY 24...

Страница 8: ...sensor connector Room temperature probe Temperature probe Temperature probe RS485 Analog input RADIANT HEATING SYSTEM WITH EXTERNAL TEMPERATURE SENSOR FOR CLIMATIC FUNCTION HOUSING UNIT HEATING COOLING SYSTEM RADIANT WITH UMIDITY CONTROL BY MEANS OF A DEHUMIDIFIER SUPPLIED WITH REFRIGERATED WATER AT LOW TEMPERATURE INSTALLATION EXAMPLES 1 Hydraulic compensator 2 System pump 3 Room thermostat 4 Ext...

Страница 9: ...YSTEM RADIANT WITH UMIDITY CONTROL BY MEANS OF A DEHUMIDIFIER SUPPLIED WITH REFRIGERATED WATER FOR RADIANT PANELS RED LED GREEN LED A Down arrow key B Up arrow key C Enter key D ON OFF key CAUTION Carry out the appropriate programming described in the following paragraphs in order to have the equipment working according to the type of system installed 1 Diverter motorised valve 2 Hydraulic compens...

Страница 10: ...tive humidity of air conditioned environment d xx calculated dew point temperature I xx system flow temperature fixed point heating mode winter C xx system flow temperature climate heating mode winter r xx external temperature SUMMER Can be displayed if parameter Sensor 1 F fixed point regulation F fixed point regulation C Climate control I tracking adjustment WINTER ...

Страница 11: ... E I HEATING h FIXED POINT CLIMATE CONTROL COOLING c FIXED POINT TRACKING ON output activated contact closed OFF output not activated contact open To access the menu when the display shows the outlet temperature to the radiant system press the B and C buttons simultaneously The display will show the E l indication Scroll the main menu with the A and B buttons Press the C button to enter the sub me...

Страница 12: ...aneously The display will show the h c flashing notice Press the A key to enter the heating programming menu The menu shows different parameters depending on the type of adjustment selected Scroll the main menu with the A and B buttons Press the C button to enter the sub menu tl h1 h2 Where XX C indicates the heating set point temperature Press A or B to set the value Press C to save the value and...

Страница 13: ...The display will show the h c flashing notice Press key B to enter the cooling and humidity pro gramming menu The menu shows different parameters depending on the type of adjustment selected Scroll the main menu with the A and B buttons Press the C button to enter the sub menu tE SenS Where XX C indicates the cooling set point temperature Press A or B to set the value Press C to save the value and...

Страница 14: ...lue and exit the sub menu The adjustment range is from 1 0 sec to 10 0 sec default 3 0 sec Where XX sec indicates the delay time of the adjustment function from the room thermostat inlet During this time the relay output is activated closure of the M3 contact Press A or B to set the value Press C to save the value and exit the sub menu The adjustment range is from 0 sec to 100 sec default 30 sec W...

Страница 15: ...by parameter P4 The motorised valve is forced on the return from the radiant system and the pump has stopped When the temperature is within the normal operating range the alarm will disappear automatically ALARM FUNCTION alarms only expected in fixed point cooling mode with relative humidity sensor and ambient temperature connected Sens parameter 1 SOTWARE RESET With the reset operation all softwa...

Страница 16: ...midity sensor ELECTRICAL CONNECTIONS TO THE ACTUATOR POWER UNIT 24V DC code AL24VDC MODBUS INTERFACE USB code USBMOD DIN RAIL INSTALLATION V in 230V 50Hz V out 24V DC I out 500 mA P out 12W TECHNICAL DATA USB 2 0 to RS485 converter Backward compatible with USB 1 1 Connection via screw terminals Baud rate supported 75 bps 115200 bps up to 6 Mbps Low power consumption no external power supply requir...

Страница 17: ... COMPARATO reserves the right to replace the Product with an identical one if the product is out of production it will be replaced with one with identical specifications provided that according to the unquestionable opinion of COMPARATO nello S r l the repair is not economically excusable Interventions and or repairs and or spare parts will not be covered by this Warranty if it turns out that they...

Страница 18: ...DIAMIX PR COMPAMIX PR 18 COMPARA TO NELLO SRL comparato com ...

Страница 19: ...DIAMIX PR COMPAMIX PR 19 COMPARA TO NELLO SRL comparato com ...

Страница 20: ......

Отзывы: