Figure 2:  Dual ECB for dual-redundant controller 
configurations

StorageWorks Model 2100 and 2200 controller enclosures use 
a different type of ECB that does not require an ECB Y-cable 
(see 

Figure 3

). These enclosures contain four ECB bays. Two 

bays support Cache A (bays A1 and A2) and two bays support 
Cache B (bays B1 and B2)—see this relationship in 

Figure 4

.

NOTE:  

No more than two ECBs are supported within a StorageWorks Model 

2100 or 2200 controller enclosure at any time—one for each array 
controller and cache set. Blanks must be installed in the remaining vacant 
ECB bays for controlling air flow.

.

Figure 3:  Status LEDs for a StorageWorks Model 2100 and 
2200 enclosure ECB

.

Figure 4:  ECB and cache module locations in a 
StorageWorks Model 2100 and 2200 enclosure

IMPORTANT:  

When replacing an ECB (see 

Figure 5

), match the vacant ECB 

bay with the supported cache module. This bay will always be next to the 
failed ECB (see 

Figure 4

).

Figure 5:  Removing an ECB that supports cache module B 
in a StorageWorks Model 2100 and 2200 enclosure

1

Battery disable switch (SHUT 
OFF)

2

Status LED

3

ECB Y-cable

4

Faceplate and controls for 
second battery (dual ECB 
configuration only)

1

ECB charged LED

2

ECB charging LED

3

ECB fault LED

CXO5713B

CACHE

POWER

ST

AT

US

SHUT OFF

CACHE

POWER

ST

AT

US

SHUT OFF

3

~

4

2

1

CXO6358A

1

2

3

1

B1 supports cache B

2

B2 supports cache B

3

A2 supports cache A

4

A1 supports cache A

5

Controller A

6

Controller B

7

Cache A

8

Cache B

CXO6864A

4

2

1

3

CXO5608B

5

6

7

8

CXO6922B 

Содержание StorageWorks HSG60

Страница 1: ...tem For instructions on upgrading a single controller configuration to a dual redundant controller configuration refer to the appropriate array controller user guide or maintenance and service guide E...

Страница 2: ...2100 and 2200 enclosure ECB Figure 4 ECB and cache module locations in a StorageWorks Model 2100 and 2200 enclosure IMPORTANT When replacing an ECB see Figure 5 match the vacant ECB bay with the supp...

Страница 3: ...n a grounded antistatic mat HSZ70 Dual Redundant Controller Configurations Use the following steps and Figure 1 or Figure 2 to replace an ECB 1 Connect a PC or terminal to the maintenance port of the...

Страница 4: ...te to replace an ECB in single controller and dual redundant controller configurations using FRUTIL 1 Connect a PC or terminal to the maintenance port of the controller that has the defective ECB The...

Страница 5: ...if desired enter current data using the following command SET THIS_CONTROLLER TIME dd mmm yyyy hh mm ss IMPORTANT An internal clock monitors the life of the ECB battery This clock must be reset after...

Страница 6: ...ins to contact ground resulting in cache module damage NOTE If an empty bay is not available place the replacement ECB on top of the enclosure or at the bottom of the rack 6 Insert the replacement ECB...

Страница 7: ...de IMPORTANT Make sure to identify the existence of this updated table in the user guide Table 1 ECB Status LED Displays LED Display ECB State Definition Startup Checking temperature and voltage If th...

Отзывы: