Fibre Channel SAN Switch 2/16 Installation Guide
C–3
Technical Specifications
Environmental Requirements
Table C–3 lists the environmental ranges that are acceptable when the SAN switch 2/16 is
operating, and the acceptable ranges when the switch is not operating.
BTU rating
170 Watts x 3.412 BTU/Hr/Watts = 580 BTU/hr
Inrush current
10 Amps Peak, > 300 usec - hot/cold start
Input line protection
Fused in both hot & neutral lines
Maximum dimensions
3.5” wide, 1.5” high, 13.5” long
Table C–2: Power Supply Specifications (Continued)
Specification
Value
Table C–3: Environmental Requirements
Condition
Acceptable Range
Temperature (operating)
10
°
C to 40
°
C
Temperature (non-operating)
-35
°
C to 65
°
C
Humidity (operating)
20% to 85% RH non condensing, at
40
°
C
Humidity (non-operating)
0% to 90% RH non-conducting, at 4
0
°C
Altitude
(operating)
0 to 3 kilometers above sea level
Altitude
(non-operating)
0 to 12 kilometers above sea level
Shock
(operating)
4G, 11MS duration, half sine
Shock
(non-operating)
20G, 11MS duration, sq.wave
Vibration
(operating)
5G, 0-3 kHz at 1.0 octave/minute
Vibration
(non-operating)
10G,
0-5kHz at 1.0 octave/minute