background image

 
 

 

Figure 8

. Load balancing at the row level 

PDR 

UPS Rack 

DPs 

60+ kVA 

15 kVA 
15 kVA 

15 kVA 

15 kVA 

 

AC 

Mains 

 

UPSs 

ITE 

Rack 

ITE 

Rack 

ITE 

Rack 

ITE 

Rack 

PDR 

UPS Rack 

DPs 

60+ kVA 

20 kVA 

20 kVA 

20 kVA 

ITE 

Rack 

ITE 

Rack 

ITE 

Rack 

 

UPSs 

Equipment row 2 

Equipment row 1 

 

 

Cable reduction 

Figure 9 shows the differences between single-phase and three-phase AC cabling. With a single-

phase distribution system, cables from each side (branch) of the neutral point are routed from 

distribution panels to equipment groups or racks. Load balancing is more difficult, requiring at least 
two distribution cables per rack and more careful planning. Racks receiving two AC buses will require 

power distribution units (PDUs) to be installed in pairs to achieve a balance of equipment loading. 

With three-phase distribution, each equipment rack requires only one cable providing three hot wires 

and one neutral conductor. Load balancing is possible with one three-phase PDU, which simplifies the 
configuration. 

 

Figure 9

. Comparison of single-phase and three-phase AC cabling with North American voltages  

(ground not shown) 

Single-phase AC cabling 

Three-phase AC cabling 

Neutral 

110 VAC 
(hot) 

Single-phase 
110 VAC 

110 VAC 
(hot) 

110 VAC  
(hot) 

110 VAC 
(hot) 

Split-phase 
208 VAC 

Split-phase 

208 VAC 

 Distribution Pan

el 

Single-phase 
110 VAC 

Neutral 

Split-phase 
208 VAC 

Bus A 

Bus B 

Split-phase 

208 VAC 

Single-phase 
110 VAC 

 Distribution Pan

el 

110 VAC 

(hot) 

To 

PDUs 

To 
PDUs 

 

9

 

Содержание 204451-002 - UPS T2200 XR

Страница 1: ...PS load considerations 5 UPS topologies single conversion versus double conversion 6 HP solution high efficiency three phase UPSs 7 Three phase power distribution technology 8 Load balancing and monit...

Страница 2: ...al load properly with facility power to ensure safe and cost efficient operation Power distribution in data centers The typical data center uses power that originates from the utility power grid and i...

Страница 3: ...tery power until utility power is restored to within the accepted operating range or until the building generator can produce the required power whichever comes first Once UPS input power resumes eith...

Страница 4: ...fits of distributing three phase power to individual racks become more significant Strictly speaking IT equipment ITE does not use three phase power1 the benefits are in its distribution These benefit...

Страница 5: ...erated by most power supply units is typically within the 47 to 64 Hz range to accommodate worldwide applications UPS must maintain output frequency within the acceptable range Power factor correction...

Страница 6: ...gure 4B includes a rectifier In normal operation the rectifier processes the AC input voltage and routes the DC to the inverter that produces the output In online operation the batteries provide the i...

Страница 7: ...t that meets load requirements When AC input power is absent the system goes into battery mode Figure 5 HP RP12000 3 UPS Figure 6 DCOD topology used in HP three phase UPSs One characteristic of the DC...

Страница 8: ...o 85 percent efficiency at the same loading Three phase power distribution technology The benefits of distributing three phase power to individual racks become significant for high density installatio...

Страница 9: ...planning Racks receiving two AC buses will require power distribution units PDUs to be installed in pairs to achieve a balance of equipment loading With three phase distribution each equipment rack re...

Страница 10: ...ferent levels of load monitoring Circuit monitoring panel provides local display of current loading at the distribution panel level Enhanced monitoring provides local display of current demand voltage...

Страница 11: ...60 kilowatts through a PD rack and power distribution cables to a high density system of four 15 kW ITE racks In this example the ITE racks use conventional air cooling as supplied through plenums in...

Страница 12: ...ts of power distributed through the HP PDR In this example the HP Modular Cooling System MCS is used to provide chilled water forced air cooling for the IT equipment The UPSs and PDR use conventional...

Страница 13: ...T equipment and power distribution products from different sources to build a complete datacenter There were always concerns of how easily efficiently and reliably components from different vendors wo...

Страница 14: ...er white papers http h18004 www1 hp com products servers technology whit epapers datacenter html Call to action Send comments about this paper to TechCom HP com 2007 Hewlett Packard Development Compan...

Отзывы: