Страница 1: ...and Installation Manual This document has been produced to accompany the Studer User and Installer Manual For any further information regarding installation or using this range of COMPACT inverters chargers please contact the engineering dept at Morven Electronics Ltd Tel 44 0 141 8103100 Fax 44 0 141 8103111 Email Sales morven co uk ...

Страница 2: ...g the Standby knob on the control panel This load can be adjusted from 1 20 watts The inverter will automatically switch ON if it detects a load present at the AC OUTLET 2 The Transfer System The COMPACT can be connected to an AC source at the AC INPUT connector e g grid system or generator The transfer system monitors this voltage and if it is within pre set limits switches OFF the inverter and t...

Страница 3: ...installation or servicing Prior to starting Installation 1 Important Ensure that the model of Compact is compatible with the battery voltage The last two digits in the model number denotes the battery voltage e g C3548 should only be connected to a 48Volt battery 2 Determine whether the batteries are sealed gel or normal lead acid batteries Set the small slider switch Equalize to the OFF position ...

Страница 4: ...he unit indicate the battery condition as 100 charged If the LED 12 marked Batt Low High is illuminated this indicates that the battery voltage is too low If the LED 12 marked Batt Low High is flashing this indicates that the battery voltage is too high If the COMPACT is connected with the incorrect battery polarity it is probable that the internal input fuse will be damaged Before attempting to r...

Страница 5: ... the front of the unit will illuminate if this relay is Active The relay can be programmed to switch due to various conditions Programming mentioned later It is factory set to operate during the following conditions 1 Over temperature 2 Overload 3 Over voltage or Under voltage on the batteries 4 If the COMPACT has been turned OFF manually or with a fault The relay can also be manually switched ON ...

Страница 6: ...w Battery Volts are too high 13 OFF Unit OFF Must be manually restarted Unit OFF Will restart automatically 14 Battery Charger in Equalisation cycle 15 18 Charge condition of battery LED15 Absorption time is running 25 CURRENT MONITOR In Inverter mode displays the output power in of Pnom In Charger mode displays charge current in Amps 200 LED indicates power sharing Push buttons 19 ON OFF Turning ...

Страница 7: ...ate continuously at its full rated power or for short periods above this rated power If the unit is operated for long periods above its maximum rating it will shut down automatically At this point the Overload LED 11 will illuminate and the OFF LED 13 will flash After 10 seconds the inverter will switch ON again automatically If the inverter is overloaded 4 times within a short period of time then...

Страница 8: ...factory settings suit most battery manufacturers charging recommendations however they can be programmed to different values if required See Programming The charger functions are shown in the diagram below 3 4 Stage battery charging algorithm Equalisation Charging Warning Equalisation mode should never be used with GEL batteries When charging Lead acid batteries the COMPACT unit will automatically...

Страница 9: ...icated on LEDs 15 18 on the control panel Led 15 Battery 75 100 Led 16 Battery 50 75 Led 17 Battery 25 50 Led 18 Battery 0 25 The Transfer system When an AC voltage is at the AC INPUT of the COMPACT the AC IN Led 1 is illuminated If this voltage is within the presettable voltage and frequency range adjustable using the TRANSFER knob described in the next section this voltage is switched directly t...

Страница 10: ...lar Charger Regulator optional The COMPACT also has an option of an integrated Solar charge regulator for charging the batteries The Solar Charge regulator works automatically and is always in operation As soon as energy is delivered from the solar modules the SOLAR CHARGE LED 3 is illuminated and energy is delivered into the batteries in the same charging regime as the battery charger The Solar R...

Страница 11: ... Auxiliary Contacts Active during 1 Over temperature 2 Overload 3 Over voltage or Under voltage on the batteries 4 If the COMPACT has been turned OFF manually or with a fault RESETTING When the COMPACT is installed the unit will operate to these default settings These settings suit most installations and users generally find that they do not need to reprogram these settings However in some situati...

Страница 12: ... hand side are illuminated LEDs 10 13 Using the table above LED 14 denotes 4 hours Press button 19 until LED 14 is illuminated Do not touch any buttons for 10 seconds and change will be saved The voltage levels and times that have been changed will not activate until the next charging cycle Charging at the incorrect voltage levels can greatly reduce the life of your battery 21 19 20 LED 10 Equalis...

Страница 13: ...erator i e when LED 18 illuminates the battery capacity is low and the generator should be started When LED 15 is illuminated the batteries are almost fully charged and the generator can be switched off Manually operating the Aux Contacts The Aux Contacts can be operated at any time by pressing the Aux Contacts button 21 LED 6 Contact Manual illuminates and LED 5 Contact active illuminates By push...

Страница 14: ...wait 10 seconds and the change will be stored Once back in the normal user mode the disabled functions are indicated by flashing LEDs Diagram of the different modes Indicates LED OFF Indicates LED Flashing Indicates LED ON 1 2 8 9 AC IN CHARGER AC OUT INVERTER 1 2 8 9 AC IN CHARGER AC OUT INVERTER 1 2 8 9 AC IN CHARGER AC OUT INVERTER 1 2 8 9 AC IN CHARGER AC OUT INVERTER All the functions are ena...

Отзывы: