Communications Specialties FIBERLINK XRD-8050 Скачать руководство пользователя страница 7

6

Signal Connections

The signal connections for the XRD-8050 follow the recommended EIA DCE
format for RS-232. These connections are described below and must be compat-
ible with the equipment being used. All signal connections are made via an
industry standard DB-25S connector.

Power Supply Connections

12 to 18 volts AC

Position 1 of 3 position terminal block

12 to 18 volts DC

Position 2 of 3 position terminal block

AC or DC Return (Common)

Position 3 of 3 position terminal block

Anti-Streaming Time-Out

The XRD-8050 contains an internal timer which will block the RS-232 input
signal to any unit in the event that a faulty data streaming condition is produced
by any traffic signal controller. This timer is triggered by the rising edge of the
RTS signal. When the pre-set time interval is exceeded, the CTS line will be
forced low and the data input to the XRD-8050 blocked, thereby preventing
system lockup. The unit will then remain in the blocked state until the RESET
button on the front panel on the unit is pressed. Only the XRD-8050 connected

Description

EIA Designation

DB-25S Pin Number

Chassis Ground

(AA)

1

Transmitted Data

(BA) (input)

2

Received Data

(BB) (output)

3

Request to Send

(CA) (input)

4

Clear to Send

(CB) (output)

5

Data Set Ready

(CC) (output)

             6 (jumped to 20)

Signal Ground

(AB)

7

Data Carrier Detect

(CF) (output)

8

Data Terminal Ready

(CD) (input)                20 (jumped to 6)

All other signal pins are not utilized.

11

XRD-8050 in RECEIVE MODE

Pin Description

Condition

1

Chassis Ground

(input/output)

0 VDC

2

Transmitted Data

(input)

Undetermined

3

Received Data

(output)

Pulses at data rate

4

Request to Send

(input)

+3.75 to +15 VDC

5

Clear to Send *

(output)

+3.75 to +15 VDC

6

Data Set Ready

(output)

Same as Pin 20

7

Signal Ground

(input/output)

0 VDC

8

Data Carrier Detect

(output)

+3.75 to +15 VDC

20

Data Terminal Ready

(input)

Jumpered to Pin 6

* Clear to Send will only remain in this state if the anti-streaming  timer has not
been triggered.

In addition to the above, check that the ANTI-STREAMING time-out interval is
correct for the data rate being used and that the MASTER/LOCAL switches are
set properly.  Also refer to both the general troubleshooting techniques and
those regarding fiber optic cable.

Содержание FIBERLINK XRD-8050

Страница 1: ...1 Rev E USER S MANUAL FIBERLINK XRD 8050 XRD 8050 RK Fiber Optic Linear Multidrop RS 232 Transmission System For Traffic Signal ControllerApplications Communiations Specialties Pte Ltd Serving the Asi...

Страница 2: ...obtained Communications Specialties before any equipment is returned by the Buyer All material must be shipped to Communications Specialties at the expense and risk of the Buyer Communications Specia...

Страница 3: ...with trained technicians to answer any interface questions as well as to render accurate timely and reliable service of our products The only maintenance that can be provided by the user is to ascert...

Страница 4: ...cator LEDs for continuous monitoring of all data transmitting and receiving functions 14 B Check Optical Connectors 1 Is the correct connector being used for the type of fiber optic cable employed Som...

Страница 5: ...or transmitting section of a transceiver 1 Is the operating power DC AC Voltages correct 2 Are the pins being used on the connector or terminal block correct 3 Is the correct signal level present at...

Страница 6: ...vided for operation at a wavelength of 850nm or 1300nm the fiber optic cable employed should be chosen so that it is optimized for operation at the appropriate wavelength When using any type of fiber...

Страница 7: ...e front panel on the unit is pressed Only the XRD 8050 connected Description EIA Designation DB 25S Pin Number Chassis Ground AA 1 Transmitted Data BA input 2 Received Data BB output 3 Request to Send...

Страница 8: ...turned ON at any time All others should be left in the OFF position 10 Indicator LEDs PWR Indicates that operating power is applied to the XRD 8050 TD1 TD2 Indicates that a high state logic signal is...

Страница 9: ...le on connectors provided on the rear on the plug in assembly The XRD 8050 RK is fully compatible with the XRD 8050 stand alone version INSTALLATION INSTRUCTIONS FOR XRD 8050 RK Rackmountable Version...

Страница 10: ...le on connectors provided on the rear on the plug in assembly The XRD 8050 RK is fully compatible with the XRD 8050 stand alone version INSTALLATION INSTRUCTIONS FOR XRD 8050 RK Rackmountable Version...

Страница 11: ...turned ON at any time All others should be left in the OFF position 10 Indicator LEDs PWR Indicates that operating power is applied to the XRD 8050 TD1 TD2 Indicates that a high state logic signal is...

Страница 12: ...e front panel on the unit is pressed Only the XRD 8050 connected Description EIA Designation DB 25S Pin Number Chassis Ground AA 1 Transmitted Data BA input 2 Received Data BB output 3 Request to Send...

Страница 13: ...vided for operation at a wavelength of 850nm or 1300nm the fiber optic cable employed should be chosen so that it is optimized for operation at the appropriate wavelength When using any type of fiber...

Страница 14: ...or transmitting section of a transceiver 1 Is the operating power DC AC Voltages correct 2 Are the pins being used on the connector or terminal block correct 3 Is the correct signal level present at...

Страница 15: ...cator LEDs for continuous monitoring of all data transmitting and receiving functions 14 B Check Optical Connectors 1 Is the correct connector being used for the type of fiber optic cable employed Som...

Страница 16: ...with trained technicians to answer any interface questions as well as to render accurate timely and reliable service of our products The only maintenance that can be provided by the user is to ascert...

Страница 17: ...obtained Communications Specialties before any equipment is returned by the Buyer All material must be shipped to Communications Specialties at the expense and risk of the Buyer Communications Specia...

Отзывы: