Instruction Sheet
Page 7 of 21
3. Locate cable-tie anchoring positions provided in upper sidewalls of shelf.
4. Route buffered building cables or PVC protected OSP fibers into shelf through oblong openings provided in
upper rear corner of sidewalls.
Use of protective spiral wrap around these fibers is highly recommended
.
Secure fiber bundle to the sidewall using cable-ties and anchor position located in item 3. Tighten cable-ties
sufficiently to restrict fiber movement but do not over tighten and cause damage to fibers.
5. Route fiber bundle into slack fiber management rings, as shown in Figure 5, so that approximately 1/2 to 1
inch (13 to 25mm) of protected fiber bundle passes through first ring. Enough slack should be left between
first fiber ring and restrained portion of bundle so that a loop is formed when mechanism is pushed back into
shelf. Spool as much slack fiber into rings as will be needed for subsequent splicing operations.
6. If no other cables are to be installed, proceed to Step 4
.