11.3 Install grounding kit
11.3.1
Install the grounding wire to the ground bar as shown in figure 1, using a socket wrench size 8.
11.3.2
Install the feeder cable (with the strain relief bracket installed) into the organizer as shown in section 10.2.
11.3.3
Install the grounding assembly on the studs of the installed strain relief bracket using a socket wrench size 8.
12
Route feeder fibers to splice tray
12.1 Route subunits to storage
12.1.1
Select the subunits that will be used for splicing to the drops or branch cable. Keep them separate. Route the
subunits that will not be used to the loop storage basket. Make sure all subunits are positioned properly under the lips.
Table below gives an overview of the capacity of the loop storage basket:
Midspan
Maximum amount of subunits stored in loop storage basket
240 cm+/- 5 cm (95.5 +/- 2 inches)
8 subunits (module 6)
200 cm+/- 5 cm (78.7 +/- 2 inches)
8 subunits (module 6)
130 cm +/- 5 cm (51.2 +/- 2 inches)
12 subunits (module 6)
2
1
3
Feeder out
Feeder in
Feeder in
Feeder out
Lorem ipsum
Feeder in
Feeder out
Subunits
12.2
Directly to splice tray rear
12.2.1
Cut the subunits at the jacket end installed on side F2 (endcut) OR cut the subunit in the middle (midcut).
The non-used end can be re-stored in the loop storage.
12.2.2
Bring the cut subunit to the splice tray (rear) and mark the stripping point. Strip the subunit to this mark and clean
all fibers per standard practice.
12.3
Via uncut fiber storage
Note: Maximum 2 subunits can enter the uncut fiber storage.
The uncut fiber storage can be used with shaved subunits or with cut subunits.
12.3.1 Shaved subunit
12.3.1.1
Bring the selected subunit to the rear of the loop storage, the uncut fiber storage.
Note
: It is important that the
selected subunit is routed first and that the bundle of subunits is installed back on top of this routed subunit.
12.3.1.2
Put the selected subunit on top of the uncut fiber storage basket and indicate the marks (stripping points) between
which the subunit should be shaved. Shave and clean the subunit per standard practice. Cut the fiber to be spliced at the
jacket end of the subunit, side F2.
remove
cover
1
stripping
point
stripping
point
subunits
endcut
midcut
+/-1 cm
0.4”
F2
F1
stripping
point
stripping
point
1
F2
F1
endcut
subunits
uncut fiber storage