Ruckus ICX 7450 Switch Hardware Installation Guide
Part Number: 53-1003899-09
Installing the Ruckus ICX 7450
Installation and safety considerations
NOTE
A stacking cable is not included in the shipping carton and must be ordered separately.
Installation and safety considerations
You can install the Ruckus ICX 7450 in the following ways:
•
As a standalone unit on a flat surface.
•
In an EIA rack using a fixed-rail rack mount kit. The optional 4-post universal rack mount kit can be ordered from your switch
retailer to support up to a 30-inch deep rack. The 4-post rack mount kit includes mid-mount and rear-mount brackets.
•
In a 2-post Telco rack using a flush-mount rack kit. The 2-post rack mount ears are included with the switch and support various
mounting positions (refer to
).
Electrical considerations
To install and operate the switch successfully, ensure compliance with the following requirements:
•
The primary outlet is correctly wired, protected by a circuit breaker, and grounded in accordance with local electrical codes.
•
The supply circuit, line fusing, and wire size are adequate, as specified by the electrical rating on the switch nameplate.
•
The power supply standards are met.
Environmental considerations
For successful installation and operation of the switch, ensure that the following environmental requirements are met:
•
Because the Ruckus ICX 7450 can be ordered with fans that move air either front to back or back to front, be sure to orient your
switch with the airflow pattern of any other devices in the rack. All equipment in the rack should force air in the same direction to
avoid intake of exhaust air.
•
Some combinations of intake and exhaust airflows may not be compatible with your environment. Consult your fan and power
supply module FRU kit to determine the correct configuration.
•
The ambient air temperature does not exceed 50°C (122°F) while the switch is operating.
Location considerations
Before installing the device, plan its location and orientation relative to other devices and equipment. Devices can be mounted in a
standard 19-inch equipment rack or on a flat surface.
The site should meet the following requirements:
•
Maintain the operating environment as specified in
“Environmental considerations”
•
The Ruckus ICX 7450 should be installed with its top and bottom covers parallel to the floor. The Ruckus ICX 7450 should not
be installed upside down.
•
Allow a minimum of 3 in. of space between the front and the back of the device and walls or other obstructions for proper airflow.
•
Allow at least 3 in. of space at the front and back of the device for the twisted-pair, fiber-optic, and power cabling.
•
Allow access for installing, cabling, and maintaining the devices.
•
Allow the status LEDs to be clearly visible.